SMB350 User’s Manual
Page 24
3.3 Setup
The follow parameters can be set on the front panel of SMB350.
RS485-1 Address-1 (default = last two digits of the serial number, 00 = 100)
RS485-1 Baud rate-1 (default 9600)
RS485-2 Address-2 (default = 1)
RS485-2 Baud rate-2 (default 9600)
CT ratio (default 1)
Modbus address (default 1)
(1) Setup procedures
Step 1.
Press and hold for 2-3 seconds to enter the setting mode.
Step 2.
Press to change different parameter setting.
Press and to change the value.
Press to change the digit.
Press and hold for 2-3 seconds to exit the setting mode.
(2) Setup range of each parameter
Modbus address : 1~254
Baud rate : 1200 / 2400 / 4800 / 9600 bps
CT ratio : 1~250 (each channel and each phase)
Address-1: 1
Baud rate-1: 9600
CT ratio setting
Channel-1A: _1
Address-2: 1
Baud rate-2: 9600