Dacor Modernist DHD Series Скачать руководство пользователя страница 3

PLANNING

GUIDE

All specifications subject to change without notice. 

www.dacor.com 

Ph. 800.793.0093

 

CAUTION

To reduce risk of fire and to properly exhaust air, duct air to the outdoors 

only (not into walls, attics, crawlspaces, or garages).

 

WARNING

During duct installation, ensure the damper flaps on top of the hood can 

open freely.

•  Local building may codes require makeup air systems for use with 

ventilation systems that move air at greater than the specified 

rate (CFM). In designing the system, consult an HVAC specialist 

for local requirements and to ensure best performance.

•  All ductwork material (incl. screws and foil tape) shall be bought 

by the customer.

•  Ductwork must not interfere with floor joists or wall studs.

•  On dual-exhaust models, the two 8” exhausts may be merged 

into one 10” duct using the optional Dacor transition kit AHT10 

(Contact Dacor Customer Assurance for details: 833-353-5483).

•  Fasten all joints with sheet-metal screws, and seal with certified 

duct/foil tape.

•  Usually, the blower vents through the hood top (A) but can be 

rotated to vent through the hood rear (B). When planning ducting, 

always find the shortest, most direct route to the outside.

Duct-Length Calculation Table

The ducting determines the hood’s maximum straight duct length.

Duct Type

Max. Duct Run

8" Round

60 feet

10" Round

50 feet

3 1/4" x 10" Rectangular

For each new elbow and transition, you must subtract “equivalent 

lengths” from your total maximum duct run length to compensate 

for wind resistance.
To determine your maximum length, start with the duct run’s total 

max. length, then subtract all of the ductwork equivalent lengths.

Modernist 30”, 36", 48" Wide

Wall Hood

Page 3 of 3

All tolerances: ±¹/₁₆” (±1.6 mm) unless otherwise stated.

DHDxx

Planning the Ductwork, cont.

A

B

Ductwork Equivalent Lengths

Piece

Subtract

8” 90° Elbow

7 feet

8” 45° Elbow

3 feet

10” 90° Elbow

5 feet

10” 45° Elbow

2 feet

3” x 10” to Round 90° Transition

25 feet

3 1/4” x 10” to 8”/10” Round Transition

4 feet

Wall Cap w/Damper

*

Roof Cap

*Equivalent lengths of roof and wall caps vary with model and configuration.

Ductwork Tips

•  Minimize transitions/turns/sharp angles (ex: two staggered 45° 

angles are better than one 90° angle).

•  Keep turns as far from the hood exhaust as possible; keep as 

much space between bends as possible.

•  For best performance, use round ducting, especially for elbows.
•  Try to keep at least 24 in. of straight duct between each elbow.
•  Avoid using “S” or back-to-back adjacent elbows.
•  In extremely cold-weather regions, use thermal breaks (i.e., short 

sections of non-metallic duct) to avoid indoor heat loss. Put the 

break as close to the outside pass-through point as possible.

•  Do not use flexible metal ducting, or ductwork smaller than what 

the tables advise.

•  The hood exhaust connects to an 8” round duct. You can increase 

the duct size over the duct run if desired. 

•  To prevent backdraft, never decrease the duct size over the run. 

If existing ductwork is less than 8 inches in diameter, replace it 

with 8” ductwork.

•  Join ducting with sheet-metal screws, then seal with certified 

duct/foil tape. Never join ducting with tape only.

•  Support the weight of the ducting with sheet-metal screws as 

needed.

•  To avoid backdraft, a damper at the duct outlet may be required.

 

WARNING

•  Have electricity to the range hood installed by a licensed electrician.

•  Observe all local codes during site preparation and installation. 

Contact your local building department for details.

•  Follow wall anchoring directions precisely to ensure the hood does 

not fall.

•  To avoid electric-shock injury and water damage, know in-wall 

utilities locations before breaching the wall.

•  Remove temporary holding brackets after anchoring the hood 

permanently.

Отзывы: