PLANNING

GUIDE

www.Dacor.com      Phone: (800) 793-0093  

Specifications subject to change without notice.

Install all appliances according to accompanying installation instructions.

8.2

ERV30, ERV36, ERV48,

PRV30, PRV36, PRV46

30”, 36”, 46”, 48” Wide,

Slim Raised Vent

Duct work Design Tips

Wherever possible, reduce the number of transitions and turns to as 

 

few sharp angles as possible. Two staggered 45° angles are better 

than one 90°. Keep turns as far away from the hood exhaust as 

possible, with as much space between each bend as possible.
For best performance, use round duct instead of rectangular when 

 

possible, especially when elbows are required.
If multiple elbows are used, try to keep a minimum of 24” of straight 

 

duct between them. Avoid “S” or “back to back” configurations of 

adjacent elbows.
Do not use flexible metal duct.

 

Calculating the Maximum Duct run Length

Do not use duct work that is smaller in cross-sectional area than the 

 

required duct sizes in the table to the right.
For best performance, keep the duct run as short as possible and 

 

never exceed the maximums stated at the right.
The maximum straight duct length for the raised vent system depends 

 

on the model of remote or in-line blower used with the vent system 

and the number of elbows and transitions used. The

 Equivalent 

Number of Feet

 for each elbow and transition (see table) must be 

subtracted from the maximum straight length to compensate for 

wind resistance. To determine the maximum allowable length of the 

duct work, subtract all of the equivalent lengths of the elbows and 

transitions from the 

Blower Maximum Duct Straight Length

.

For example, for a raised vent system using 3 1/4” X 10” rectangular 

duct, two (2) 3 1/4” X 10” 90° elbows, a 3 1/4” X 10” rectangular to 10” 

round transition, and a rEMP16 remote blower:

From the 

 

Blower Maximum Duct Straight Length

 table, the 

maximum length without transitions and elbows is 60 feet.
The equivalent length of each 90

 

°

 elbow is 15 feet.

The equivalent length of 45

 

°

 elbow is 2 feet.

The equivalent length of the transition is 4 feet.

 

The total equivalent length of the above components is: 15 feet + 15 

 

feet + 4 feet + 2 feet = 36 feet.
The maximum amount of straight duct that can be used with a 

 

REMP16 and the above components is: 60 feet - 34 feet = 24 feet.

Equivalent number of Feet - 

Duct Elbows and Transitions

45° elbow 

8 Inch

3 feet

3 ¼” X 10 

45° elbow

7 feet

45° elbow

10 Inch

2 feet

3 ¼” X 10 

90° elbow

15 feet

90° elbow 

8 Inch

7 feet

3 ¼” X 10 

90° flat elbow

20 feet

90° elbow

10 Inch”

5 feet

3 ¼” X 10  

to 8” round

transition

4 feet

90° 3 ¼” X 10 to 8” 

round

transition

25 feet

3 ¼” X 10  

to 10” round

transition

4 feet

Roof cap

*

Wall cap

*

* The equivalent lengths of roof and wall caps vary with model and 

configuration. For equivalent length, contact the manufacturer or a qualified 

HVAC specialist.

Document # PG08-001

Revised 03/29/10   Page 2/3

raised Vent 

Model no.

approved Dacor 

Blowers* 

ERV/PRV30

Remote blowers: 

REMP3 or REMP16

In-line blowers: 

ILHSF8 or ILHSF10

ERV/PRV36

PRV46
ERV48

*For detailed information on the remote/in-line blowers,  

refer to the blower installation instructions.

Duct Size 

Used

Blower Maximum Duct Straight Length

rEMP3 remote Blower

rEMP16 remote Blower

iLHSF8 in-line Blower

iLHSF10 in-line Blower

8 Inch

50 feet (15.2 meters)

60 feet (18.3 meters)

50 feet (15.2 meters)

60 feet (18.3 meters)

10 Inch

40 feet (12.2 meters)

70 feet (21.3 meters)

40 feet (12.2 meters)

70 feet (21.3 meters)

3 ¼” X 10”

40 feet (12.2 meters)

60 feet (18.3 meters)

40 feet (12.2 meters)

60 feet (18.3 meters)