4
NOTES:
1. Best performance is achieved by
using round duct instead of rect-
angular, especially when elbows
are required.
2. If multiple elbows are needed,
ensure that there is a minimum
of 24” of straight duct between
any two elbows.
3. Avoid “S” or “back to back” con-
figurations caused by adjacent
elbows.
4. Thermal breaks, such as a short
section of non-metallic duct,
should be used in areas of
extreme cold.
5. A back-draft damper at the duct
outlet may also be required.
6. Do not use flexible metal duct.
7. Do not use duct work that is
smaller in cross-sectional area
than the recommended size
duct.
8. Do not rely on duct tape alone to
seal duct joints. Use sheet metal
screws as require to support the
duct weight.
9. The vent hood and cooking
appliance(s) must be removable
if service is required.
10. Be certain that the duct work
does not interfere with floor
joists or wall studs.
11. It is important to keep as few
turns in the duct run, and to keep
the run as short as possible.
12. EhDR series hoods are not
equipped with an internal blower.
Installation of an in-line (Dacor
model ILB8) or remote
blower (Dacor model
REMP3) is required.
Install the in-line or
remote blower according
to the blower installa-
tion instructions before
installing the hood.
13. If installing an in-line
blower, it must be locat-
ed within 60 equivalent
feet of the hood canopy
system.
Model
Series
Duct
Size
Maximum Equivalent
Straight Lengths
Internal
Blower
ILB8
REMP3
EHD
MHD
8” Round
60’
NA
NA
10” Round
50’
NA
NA
3 1/4” x 10”
50’
NA
NA
EHDR
MHDR
8” Round
NA
60’
60’
10” Round
NA
50’
50’
3 1/4” x 10”
NA
50’
50’
Recommended Maximum Straight Lengths
3 1/4" x 10"
90° Elbow
3 1/4" x 10"
45° Elbow
Roof Cap or
Wall Cap with Damper
3 1/4" x 10"
90° Flat Elbow
Transistion
3 1/4" x 10" to Round
45° Elbow
Round Duct
90° Transistion
3 1/4" x 10" to
8" Round
90° Elbow
Round Duct
15 Feet
7 Feet
30 Feet
20 Feet
8" Diameter - 4 Feet
10" Diameter - 4 Feet
8" Diameter - 3 Feet
10" Diameter - 2 Feet
25 Feet
8" Diameter - 7 Feet
10" Diameter - 5 Feet
Recommended sheet metal elbows, transition, and wall cap
equivalent straight lengths
Electrical Power Supply
Requirements
NOTES:
1. If the power supply
requirements shown do
not agree with those listed
on the product data plate,
provide a power source per
the information found on the
product data plate.
2. If the electrical service
provided does not meet the
product specification, or
does not conform to the NEC
or local standards, do not
proceed with the installation.
Call a licensed electrician to
correct the electrical service
before proceeding.
Electrical Supply Requirements
120 Vac, 60 Hz, 15 Amp. Dedicated
Circuit
Total Connected Load
1.4 kW (12 A)
The correct voltage, frequency and amper-
age must be supplied to the appliance from
a separate, grounded, circuit that is pro-
tected by a properly sized circuit breaker
or time delay fuse. Refer to the data plate
located on the blower housing, inside the
filter area. The specifications below are
provided for reference and do not super-
sede the information on the product data
plate.
Refer to the table below for recommended
maximum straight lengths of duct to pro-
vide adequate performance. Refer to the
table above for recommended sheet metal
elbows, transitions, and wall cap equivalent
straight lengths.
3. It is the owner’s responsibility
to ensure that electrical
installation of this appliance
is performed by a qualified
electrician. The electrical
installation must comply
with the National Electric
Code ANSI/NFPA 70-1990 (or
to latest revision) and local
codes and ordinances.
4. Failure to disconnect electric
power may result in electrical
shock or fire hazard.