PLANNING

GUIDE

DR30D, DR30DH, DR30DI, DR30DIH

Distinctive 30” Wide 

Dual Fuel Range

Document # PG05-006

Revised 12/11/14   Page 2/6

Ranges equipped for installation in Canada:

 

Freestanding ranges used in Canada require 

a factory installed 4-wire appliance cord and 

NEMA 14-50P plug. Order model number 

DR30D-C or DR30DH-C. The appliance cord is   

66 inch (168 cm) long.

 

Do not modify the factory wiring. The plug is 

designed to plug directly into a NEMA 14-50R 

electrical receptacle installed by a licensed 

electrician.

All other models:

The wiring needs to be long enough to allow the range to be pulled out for 

service, while remaining connected (see following page).
The wiring connected to the range must:

 

Meet NEMA standards and have a minimum rating of 250 Volts @ 30 

Amp.

 

Include a strain relief.

 

Be terminated by tinned leads, closed loop terminals or open ended 

spade lugs with upturned ends.

 

Connect to a junction box or receptacle installed by a licensed 

electrician.

Where local code permits, a 3 or 4 wire appliance cord may be used. It 

must:

 

Be UL listed type SRD or SRDT.

 

Be equipped with a NEMA 14-50P 4-wire plug or, where local code 

permits, a NEMA 10-50P 3-wire plug.

Electrical Specifications

Circuit Required

Total Connected Load

240 Vac, 60 Hz., 30 Amp.*

5.7 kW (23.8 Amp.)

 

The ratings above are for reference only - refer to the range's product 

data label for exact specifications.

 

The correct voltage, frequency and amperage must be supplied to 

the appliance from a separate, grounded, circuit that is protected by a 

properly sized circuit breaker or time delay fuse. If a time-delay fuse is 

utilized, fuse both sides of the line (L1 and L2).

* Two 120 Vac hot (L1 and L2), one neutral, one ground

The regulator inlet accommodates a 3/4” gas line. The range ships with a 

1/2” to 3/4” adapter connected to the regulator.

Gas and Electrical Requirements

A

B

C

D

4 3/4”

(12.1 cm)

22 1/8”

(56.2 cm)

8 3/4”

(22.2 cm)

13 3/4”

(34.9 cm)

B

Gas 

inlet

A

C

7/8” (2.2 cm) dia. electrical 

connection hole in bottom*

D

Range electrical access, 

cover removed

GAS AND ELECTRICAL DIMENSIONS

Gas Supply Pressure Requirements*

Gas Type

Manifold Pressure

Minimum Gas Supply 

Pressure

Natural gas

5” water column

6” water column

LP

10” water column

11” water column

* Maximum input gas supply pressure for all models is 1/2 psi

7/8" to 1 1/8" dia. access hole

NEMA 14-50R 

RECEPTACLE