background image

5. SWITCH explanation

ZERO KEY 

: If press 3 seconds, set to 4mA automatically. 

SET KEY 

: Calibration KEY 

UP KEY 

: At Calibration, output rise (At one touch, 5 μ A rise) 

DOWN KEY 

: At Calibration, output fall (At one touch, 5μA fall) 

  (If press UP, DOWN key long, change of output grows) 

6. CALIBRATION

 To calibrate load cell and AM130, 

the  standard  weight  need  more  than  30%  of  full 

capacity.

 

If press 3 seconds 

RUN LED off 

ZERO LED on 

↓ 

When  it  is  no  load  to  Load  cell,  please    set  to  4mA  by  UP 

key and DOWN key. 

↓ 

ZERO LED off 

↓ 

When  give  load  more  than  30%  of  Load  cell  capacity, SPAN 

LAMP becomes ON. 

 

Adjust to 20 mA (or required mA) with the UP key and 

DOWN key.

↓ 

Calibration END 

Отзывы: