ENGLISH
10
Page 13.0
On page 13.0 you can set the system status in
ON, OFF or controlled by a remote signal EXT
(digital input IN1).
If ON is selected the pump is always on.
If OFF is selected the pump is always off.
If EXT is selected, reading of the status of digital
input IN1 is enabled. When input IN1 is
energised the system goes ON and the pump is
started (on the Home Page the messages
“EXT” and “ON” appear alternately at bottom
right); when input IN1 is not energised the
system goes OFF and the pump goes off (on
the Home Page the messages “EXT” and “OFF”
appear alternately at bottom right).
For the connection of the inputs see par. 5.1.1