ENGLISH
91
Table 32: Factory settings
Default settings
M/M M/T T/T
Installation
note
Identifier
Description
Value
LA Language ITA
ITA
ITA
SP
Setpoint pressure [bar]
3,0
3,0
3,0
P1
Setpoint P1 [bar]
2,0
2,0
2,0
P2
Setpoint P2 [bar]
2,5
2,5
2,5
P3
Setpoint P3 [bar]
3,5
3,5
3,5
FP
Test frequency in manual mode
40,0
40,0
40,0
RC
Rated current of electric pump [A
0,0
0,0
0,0
RT
Direction of rotation
0 (UVW)
0 (UVW)
0 (UVW)
FN
Rated frequency [Hz]
50,0
50,0
50,0
OD
Type of system
1 (
Rigid )
1 (
Rigid )
1 (
Rigid )
RP
Pressure drop for restart [bar]
0,5
0,5
0,5
AD Address
0
(Auto)
0 (Auto)
0 (Auto)
PR Pressure
sensor
remote
0
(Absent)
0 (Absent)
0 (Absent)
MS Measurement
system
0
(International )
0
(International )
0
(Internazional)
SX
Maximum setpoint [bar]
9
9 for size
4.7A
13 for size
10.5A
13
TB
Delay for water failure block [s]
10
10
10
T1
Shutdown delay [s]
2
2
2
T2
Shutdown delay [s]
10
10
10
GP Proportional
gain
coefficient 0,6
0,6
0,6
GI
Integral gain coefficient
1,2
1,2
1,2
FS
Maximum rotation frequency [Hz]
50,0
50,0
50,0
FL
Minimum rotation frequency [Hz]
0,0
0,0
0,0
NA Active
inverters N N N
NC Simultaneous
inverters NA NA NA
IC Reserve
configuration
1
(Auto)
1 (Auto)
1 (Auto)
ET
Exchange time [h]
2
2
2
CF Carrier
[kHz] 20
10
5
AC Acceleration 5
5
4
AY
Anti cycling
0 ( Disabled )
0 ( Disabled )
0 ( Disabled )
AE
Anti-blocking function
1( enabled )
1( enabled )
1( enabled )
I1
Function I1
1 (float )
1 (float )
1 (float )
I2
Function I2
3 (P Aux)
3 (P Aux)
3 (P Aux)
I3
Function I3
5 (Disabled)
5 (Disabled)
5 (Disabled)
O1
Output 1 function
2
2
2
O2
Output 2 function
2
2
2
SF
Starting frequency [Hz]
FN
FN
FN
ST
Starting time [s]
1
1
1
PW Password
settings 0 0 0