Operational faults
Fire alarm interface

:

• 

Confirm signal from interface is normally open volt free.

• 

1kΩ triggering resistor and 10kΩ end of line resistor installed as detailed on previous page.

Smoke detector

:

• 

10kΩ end of line resistor is installed as detailed on previous page.

•  Turn smoke detector head clockwise until a click is heard and a physical connection is made between head 

and base.

Additional breakglass

:

• 

10kΩ end of line resistor installed and connections as detailed on previous page.

• 

Confirm the breakglass terminal connector is firmly secured onto the PCB.

Drive

:

•  Check MOT terminal connections in the control panel and local connection point.

•  Test power supply from terminals a and b in control panel, minimum of 24v DC should be present on 

operation (fire).

•  If voltage is present on operation and connections are correct, the issue is with the drive(s) and not the 

controls. See drive instructions for assistance. 

DIP-Switches

:

•  For operational set-up (including one-touch reset of system and activation of integrated ventilation buttons) 

see information on reverse of white control panel board.

Natural ventilation operation (optional)

Only operates when DIP-Switch 8 is on. Integrated ventilation buttons:

RZN 4503-T Troubleshooting Guide

Light indicates

vent open

Press to

close vent

Press to

open vent