Intended use
- SHEV control panel for small up to medium sized
building objects
- Applicable in the AdComNet® SHEV bus system
- Microprocessor based control panel
- 2 line, 3 group
- 16 A actuating current
- Comfort functions for daily ventilation
-
Only for inside mounting
Operating voltage 230 V AC!
Risk of injury from electric shock!
- Connection has to be carried out only by an
authorized electrical specialist
- Only for inside mounting
- Just use unchanged original D+H parts
Safety notes
Smoke gases are to be carried off as unhindered
as possible through smoke and heat vent opening
in case of fire. Size, kind and arrangement of the
opening is of decisive significance for an optimal
effect of the smoke and heat vent system.
These requirements are defined in the relevant
regulations of the respective country.
More informations, are also available under
www.rwa-heute.de
.
The SHEV opening should be coordinated with the
responsible fire protection authority.
SHEV opening
An overdue maintenance of the system will be
indicated by the control panel after about ca. 14 to
16 months.
LED in the smoke vent button and the green LED
(D6) in the control panel will start flashing.
A malfunction of the smoke vent system will be still
indicated by the extinction of the green LED in the
smoke vent button.
After the maintenance time is expired (approx. 14
to 16 months), the ventilation function OPEN can
be interrupted depending on the presetting of the
service timer.
Attention: Reset of the service timer can be
carried out by a specialist company only, who
has been authorized by the appliance
manufacturer.
Servicetimer
Inspection and maintenance has to be carried out
according to D+H maintenance notes. Only original
D+H spare parts may be used. Repair is to be
carried out exclusively by D+H.
Wipe away debris or contamination with a dry, soft
cloth.
Do not use cleaning agents or solvents.
Repair and cleaning
Electrical devices, accessories, batteries and packa-
ging should be sorted for environmental-friendly
recycling.
Do not dispose electrical devices and
batteries into household waste!
Only for EC countries:
According the European Guideline
2002/96/EC for waste electrical and
electronic equipment and its implemen-
tation into national right, electrcal devices that are no
longer usable must be collected separately and
disposed of in an environmentally correct manner.
Disposal
We declare under our sole responsibility that the
product described under “Technical Data” is in
conformity with the following directives:
2004/108/EC, 2006/95/EC, 89/106/EC
Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek
Thomas Kern
Maik Schmees
Member of the Board
Authorized signatory,
Technical Director
22.12.2010
Declaration of Conformity
Observe regulations for danger warning systems
VDE 0833, guidelines for electrical systems VdS
2221, VDE 0100, DIN 18232 for smoke and heat
vent systems, regulations of the local fire-brigade
and of EVU for connection to mains supply.
Important regulations
Type
RZN 4416-M
Power supply
230 V AC, 50 Hz
Rated power
500 VA
Stand-by operating
13,6 W
Output voltage
24 V DC (21,6 - 28,5 V)
Ripple
2 Vss, load-dependent
Output rated current
16 A
Number of lines / groups *
2 / 3
Fire detector per line
max. 14 pcs.
SHEV button per Line
max. 8 pcs.
Current per group **
max. 8 A
Mode of operation
- Monitoring
continuous duty
- Alarm / ventilation
Short-time duty (30 % DC)
Housing
Steel sheet
Colour
light grey
Ingress protection
IP 54
Protection class
I
Temperature range
-5 ... +40 °C
Dimensions WxHxD
500 x 500 x 210 mm
* D+H Highspeed (HS) drives will be supported.
** The total current of the control panel must not be exceeded.
Technical data
24 V - Emergency supply
Emergency power supply for 72 hours.
Use VdS approved storage batteries only!
2x 12V / 7,0 Ah ±0,3Ah (Type 3)
With connection of D+H alarm devices:
2x 12V / 12 Ah ±0,3Ah (Type 4)
Battery control - TID
T
Temperature-guided charging of accumulator
I
Impedance measuring
Internal resistance of accumulator will be
measured cyclically. For example, if a total
discharged accumulator is connected to the
control panel = malfunction (LED on PCB)
D
Discharge control
In case of power failure and total discharge of
accumulator, the control panel will switch off.
In this case, smoke vent is no longer ensured.
In this case a malfunction will be no more
indicated either.
+
–
+
-
+
2x 12 V
-
SHEV alarm
Malfunction
Mains existing
Vent button function "OPEN"
Smoke-/ vent button function "CLOSE"
Charging voltage regulator
Ground short
OPEN running time limitation
ventilation time limitation
Pictogram explanation
D+H window drive
OK
Control panel O.K.
min
15
2
45
30
sec
20
2
60
40
English
English