Intended use
- Chain drive for electric opening and closing of
windows and flaps in the facade and roof area
- By VdS is the maximum stroke for the chain
at pressure = 600 mm and at tension = 1000 mm
- Operating voltage 24 VDC
- useable for smoke ventilation, D+H Euro-SHEV
according to DIN EN 12101-2 as well as daily
natural ventilation
- Only for inside mounting
Dimensions
Stroke
250
195,5
369
421
496
546
596
247,5
322,5
372,5
422,5
350
500
600
700
A
B
Stroke
646
472,5
800
A
B
526,5
700
750
802
852
902
576,5
628,5
678,5
728,5
900
1000
1100
1200
1300
B
173,5 mm
A
40 mm
51 mm
Observe maximum pressure load of the chain!
Maximum pressure load of the chain is not
automatically identical with maximum pressure force
of the drive!
Pressure load diagram
KA 54
KA 34
100
200
300
400
500
600
700
800
500
400
300
200
100
0
max.
Load
(N)
Stroke / (mm)
99.823.88 2.0/11/09
5/12
English
Mounting informations
Performance features
Safety notes
Operating voltage 24 VDC!
Observe enclosed red safety slip!
Do not connect directly to the mains supply!
- Connection has to be carried out only by an
authorized electrical specialist.
- Danger of violent pressure in handaccessible area.
- Keep away People from the operating area of the
drive.
- Keep away children from the control.
- Observe pressure load diagram of the chain!
- Use only in dry rooms.
- Only for inside mounting.
Use rain detector with danger of rain
(e.g. at domelights or roof windows).
- This product may not be operated without the
covering stoppers, which are delivered with
bracket sets.
- Just use unchanged original D+H parts.
- Observe mounting instructions of bracket set!
Drive unit with 2,5 m silicone cable. Dependent on
the type of window, different bracket sets are
available separately.
Extent of supply
At vertical active pulling application (e.g. for a
skylight) the forces must be rearranged by PLP1
and PDA service tool.
- microprocessor controlled electronics
- adjusting of stroke with PLP1 directly at the drive
via Powerline (PLP1
and PDA service tool))
- SHEV-high speed function (fast-running
feature in OPEN-direction)
- anti pitch function for the main closing edge
- especially silent in ventilation operation
because of reduced motor speed
- power supply is possible from both sides
- locking relief after closing
- individually programmable
KA 34 / KA 54