6/16
English
FRA 11-BSY+
99.823.20 2.2/10/12
Operating voltage 24 V DC!
Observe enclosed red safety slip!
Do not connect directly to the mains supply!
- Connection has to be carried out only by an
authorized electrical specialist.
- Danger of violent pressure in handaccessible area.
- Keep away People from the operating area of the
drive.
- Keep away children from the control.
- Use only in dry rooms.
- Only for inside mounting.
- Just use unchanged original D+H parts.
- Observe mounting instructions of drive!
Functional description
See page 1:
a
window locking bar drive FRA 11-BSY+
a1 release button with position indication
a2 LED status display
b
base plate
c
clamp (6 pole)
d
fixing clip
e
lock washer
f
square shaft (7 mm x 7 mm) l= 50 mm
g
square shaft (7 mm x 7 mm) l= 35,5 mm
h
connecting cable 2,5 m (5 pole)
Scope of supply
Intended use
Safety notes
Content
Type
FRA 11-BSY+
Power supply
24 V DC ± 15 %
Nominal current
1 A
Torque
10 Nm
Breaking load square shaft 30 Nm
Turning angle
90° or 180°Running
time
approx. 8 sek./ 180°
Lifetime
> 10.000 cycles
Duty cycle
30% (cycle time 10 min.)
Ingress protection
IP 40
Temperature range
-5°C...+75°C
Connection
2,5 m silicone cable
Switching current drive
max. 1,5 A
Loop-through contacts
60 V / 1 A
Technical data
- Drive for locking and unlocking of
standard lock fittings
- The locking unit is mounted in lieu of the
window handle and it is automatically locking
the window after closing
- Burglar and weather protection is kept
- In conjunction with D+H window drives it is
suitable as complete remote control for
windows and flaps
- Integrated electronics will control the
connnected window drive
- Operating voltage 24 V DC
- Useable for smoke ventilation, D+H Euro-SHEV
according to DIN EN 12101-2 as well as daily
natural ventilation
- Up to 4 FRA 11-BSY+ drives synchronizable
- Locking direction at the drive adjustable
- Individually programmable via software
SW-BSY+
- Only for inside mounting
The FRA 11-BSY+ will unlock the lock-sliding
fitting, after distribution voltage has been applied in
.
After reaching the end position, the window drive
will be triggered, which will open the window then.
The window drive will close the window, after
supply voltage has been applied in
. By the BSY+ bus ot the BRV indication of
the connected D+H window drive, the closed
window will be recognized and the FRA 11-BSY+
will lock the lock fitting.
For simple dismounting of FRA 11-BSY+ in any
position from the window wing or facilitating
operating of the window in case of power failure,
the drive will relieve the square shaft in the fitting
gear by a short reverse travel.
The connected D+H window drive will be switched
idle after 3 minutes.
direction OPEN
direction
CLOSE
Intended use...........................................................6
Safety notes............................................................6
Functional description.............................................6
Technical data.........................................................6
Scope of supply ......................................................6
Mounting informations ............................................7
Position indicator ....................................................7
LED status display ..................................................7
Emergency unlocking .............................................7
DIP switch settings..................................................8
Trouble shooting .....................................................9
Maintenance and cleaning ......................................9
Guarantee ..............................................................9
Declaration of Conformity .......................................9
Disposal .................................................................9
Mounting ........................................................10 - 11
Connection.....................................................12 - 15
Dimensions ..........................................................16