background image

DU
AL
 

HEA

TING & COOLING 

CONTROLLER

 

www

.theaquariumsolution.

com

 

5

To start adding a custom control program press the ‘

SET

’ button. The display will flash 

to indicate that the settings can be changed. If no buttons are pressed for 15 seconds 

the display will stop flashing and return to normal operation mode, the last setting 

shown on the screen will be saved. To return to the desired settings option press the 

set button to scroll through until the relevant symbol is shown on the left hand side.

1. 

Setting the target temperature

When the display is flashing and no symbols are shown on the left hand side choose 

the target temperature for the aquarium. This can be done by pressing the up and 

down keys until the desired temperature is displayed. Once done confirm by pressing 

the ‘SET’ button. 

2. 

Setting the cooling differential

 

The snowflake symbol should be flashing on the top left of the screen to indicate that 

the cooling differential can be set between 0.3 and 2.0ºC. Using the up and down 

arrows select how far above the set temperature you want the aquarium to reach 

before the cooling socket is activated. Press the ‘

SET

’ button to confirm.

3. 

Setting the heating differential 

The sun symbol will flash on the middle left of the screen to indicate that the 

heating differential can be set between 0.3 and 2.0ºC. Using the up and down arrows 

select how far below the set temperature you want the aquarium to be before the 

heating socket is activated. Press the ‘

SET

’ button to confirm.

4. 

Setting the alarm function 

The alarm symbol will flash on the bottom left of the screen. Using the up and down 

arrows set how far from the target temperature the aquarium can be before the 

unit will alarm. This should be set to a larger number than your heating and cooling 

differential settings. Press the ‘

SET

’ button to confirm and exit the settings. The display 

should stop flashing and will be showing the current tank temperature.

Example setup 

- The target temperature is  25.0°C +/- 0.3°C, with an alarm set for 25°C 

+/- 0.7°C.

• 

The target temperature is set to 25.0°C

• 

The cooling differential is set to 0.3°C

• 

The heating differential is set to 0.3°C

• 

The alarm differential is set to 0.7°C

When the temperature in the aquarium rises above 25.3°C, the cooling power socket 

will be energized and the attached fan/chiller will switch on (after 3 minute short 

cycle delay). The cooling power socket will remain on until the aquarium temperature 

reaches 25.0°C.
When the temperature in the aquarium falls below 24.7°C, the heating power socket 

will be energized and the attached heater will switch on. The heating power socket will 

remain energised until the aquarium temperature reaches 25.0°C. 
If the aquarium temperature falls below 24.3°C or rises above 25.7°C, the alarm will 

activate displaying the flashing alarm icon and sounding an audible alarm.

Содержание DUAL HEATING & COOLING CONTROLLER

Страница 1: ...P R O D U C T I N S T R U C T I O N M A N U A L DUAL HEATING COOLING CONTROLLER...

Страница 2: ...alarm function Alarm setting range 0 5 5 C from set point Display resolution 0 1 C Accuracy 1 C NTC Sensor with 2m cable Heating control resistive load e g heater max 1600w Cooling control inductive...

Страница 3: ...chiller The maximum rating for the socket is 1600w but it is important that if a refrigerant chiller is used its operating power is no more than 600w otherwise it may damage the control socket This is...

Страница 4: ...er outlet socket OPERATION Controller is displaying snowflake symbol ON The cooling power socket has been activated and will operate a device if plugged in to it FLASHING The cooling socket is in stan...

Страница 5: ...3 and 2 0 C Using the up and down arrows select how far below the set temperature you want the aquarium to be before the heating socket is activated Press the SET button to confirm 4 Setting the alar...

Страница 6: ...unit is steady decide how much you want to offset the reading by For example if the Dual Heating and Cooling Controller is reading 26 2 C and the temperature readout you want it to match is 26 C then...

Страница 7: ...thin the set heating and cooling differentials Check probe is in the correct position as per instructions and make sure it is submerged Temperature reading suddenly changes after a water change or whe...

Страница 8: ...s Alarms 0 5 5 C vom Sollwert Aufl sung der Anzeige 0 1 C Messgenauigkeit 1 C NTC Sensor mit 2m Kabel Regelung der Heizung ohmsche Last z B Heizger t max 1600W Regelung der K hlung induktive Last z B...

Страница 9: ...chtig funktioniert An der K hlsteckdose die mit einem II und dem Schneeflockensymbol gekennzeichnet ist kann ein Ventilator f r Verdunstungsk hlung oder ein K hlaggregat betrieben werden Die maximale...

Страница 10: ...Steckdose eingeschaltet wird Wenn Sie ein geeignetes K hlger t verwenden m chten schlie en Sie es an die mit dem Symbol II und dem Schneeflockensymbol gekennzeichnete Steckdose an Wenn das K hlger t b...

Страница 11: ...gen Sie die Einstellung durch Dr cken der Taste SET 2 Einstellung der K hlungsdifferenz Das blinkende Schneeflocken Symbol oben links auf dem Bildschirm zeigt an dass die Differenz f r die K hlung zwi...

Страница 12: ...Duale Heiz und K hlregler ist werkseitig kalibriert und sollte keine weiteren Einstellungen ben tigen Es ist jedoch m glich die angezeigte Temperatur um 1 5 C zu ndern falls gew nscht Um diese Einste...

Страница 13: ...armeinstellungen so dass sie nicht innerhalb der eingestellten Heiz und K hlparameter liegen Pr fen Sie ob die Sonde gem den Anweisungen richtig positioniert ist und ob sie eingetaucht ist Die Tempera...

Страница 14: ...ge de r glage d alarme 0 5 5 C du point de consigne R solution de l affichage 0 1 C Pr cision 1 C Capteur NTC avec 2m de c ble Contr le du chauffage charge r sistive par ex r chauffeur max 1600W Contr...

Страница 15: ...p rieure celle du r gulateur sinon il ne fonctionnera pas correctement La prise de refroidissement marqu e d un II et du symbole du flocon de neige peut faire fonctionner un ventilateur pour le refroi...

Страница 16: ...inon il ne fonctionnera pas lorsque la prise sera allum e Si vous souhaitez utiliser un l ment de refroidissement branchez le dans la prise marqu e du symbole II et flocon de neige Si le dispositif es...

Страница 17: ...Une fois cette op ration termin e confirmez en appuyant sur le bouton SET 2 R glage du diff rentiel de refroidissement Le symbole du flocon de neige doit clignoter en haut gauche de l cran pour indiq...

Страница 18: ...e la temp rature du capteur soit entre 24 3 et 25 7 C ETALONNAGE Le r gulateur double fonction chauffage et refroidissement est talonn en usine et ne devrait pas n cessiter d autres r glages Il est to...

Страница 19: ...ra ne des lectures erron es Modifiez l alarme afin que les r glages ne tombent pas dans les param tres de chauffage et de refroidissement d finis V rifiez que la sonde est correctement positionn e sel...

Страница 20: ...TheAquariumSoln fb com theaquariumsolution FOLLOW US FOR INSPIRATION www theaquariumsolution com...

Отзывы: