EN / CZone® Meter Interface (MI) User & Installation Manual
8
DIPSWITCH
•
Using a small screwdriver, carefully set the dipswitch to required setting.
•
The dipswitch number must be unique for all modules on the CZone network and must match the dipswitch
setting in the configuration to function correctly.
INITIAL POWER UP
1. Check all plugs are securely seated and connections are tight.
2. Power up the NMEA2000 network.
3. Check that the NMEA2000 Network LED lights up. It may also be flashing if other devices are present and
transmitting data.
4. Check that the Power indicator LED is green.
5. Check the circuit’s status LEDs for each individual circuit. Refer to LED codes to diagnose any faults which
need to be rectified.
6. Check the software version on the Meter Interface with the CZone Configuration Tool and update if
necessary.
7. Refer to the CZone Configuration Tool Instructions for details on how to configure and calibrate the Meter
Interface inputs.
8. Write configuration file to the Meter Interface and the rest of the CZone modules on the system.
9. Test all inputs for configured functionality.
Figure 3. Dipswitch Setting
The example shows a dipswitch number of 10000000 where 0 = Off and 1 = On.