background image

 
Cypress Envirosystems 
Doc # 152-10201-01 Rev 2.0  

BBS User Manual 

Page 15 

WGR Configuration - Min 

Minimum gauge value for the WGR 

WGR Configuration - Max 

Maximum gauge value for the WGR 

WTR  Configuration 

Select this radio button if configuring a WTR type node.  Use this for 
WFM and WSTM nodes as well 

WTR  Configuration – Log 
Scale 

Select this check box if the reading needs to be calculated in Log scale 

WTR Device Type 

Select the proper WTR type for the device 

WTR Sensor Type 

Select this for  to specify the right sensor type. Based on the readings 
select the sensor type. E.g. in case of Freezer WTR, reading1 is current 
sensor1 and sensor type is OPT1-2, Reading2 is current sensor2 and the 
sensor type is OPT1-2, Reading3 is Thermocouple and sensor type is 
Thermocouple Type-K, Reading4 is Door switch, can be set to OPT1-2. 
For Binary unit type sensor type is ignored. 

Sensor Responsivity -  
Volts or mA1, Volts or 
mA2, Value1, Value2 

Select this to calculate slope and intercept values in y= mx+B 
Enter these readings for calculating the slope and intercept. This will be 
used later to calculate the Min and Max values and engineering reading. 
These can be either noted down from the data sheet or the actual 
reading from the device. E.g. For WTR type 0-10 V, Volts1 = 0, Volts2 
=10.35, Value1 = 0.0001, Value2 = 1000 

WTR One-Point Calibration 

Check this box if a 1 point calibration can be done. This is typically used 
for calibrating thermocouples. 

One Point Calibration – 
Value Measured , 
Value desired, Cold 
junction 

Use this to apply the offset correction value to the ADC readings. . e.g. 
Temp measured might be 40 C. And user might say the right temp is 
45C. Then enter the inputs here to calculate the gain constant 
(correction factor) that is used internally for the correction 

Ok 

Save data, but keep window open 

Close  

Don’t save any data, just close dialog 

Refresh 

Get the latest data from the database 

Table 3 describes the node configuration parameters for the WGR and WTR. After adding the parameters, 
the 

Ok

  button  must  be  clicked  to  save  the  data.    Each  WGR  and  each  channel  of  a  WTR  must  be 

configured separately. For 2 channel WTRs, use the Node ID assigned when configuring the device with a  
 
 

Available Node List 

Nodes that can be seen by the BBS but have not been configured. 

NodeID 

NodeID of the Cypress Envirosystems field device 

Device ID 

A unique identifier for a WTR device.  If the user does not input a value, 
the default is the NodeID number. 

Содержание Blue Box Server

Страница 1: ...Blue Box Server User Manual Doc 152 10201 01 Revision 2 0 Sept 2010...

Страница 2: ...S FOR A PARTICULAR PURPOSE Cypress Envirosystems reserves the right to make changes without further notice to the materials described herein Cypress Envirosystems does not assume any liability arising...

Страница 3: ...le 7 5 1 Starting the Program and General Navigation 7 5 2 Readings Page 7 5 3 Other Readings Pages 9 5 4 Configuring Nodes 11 5 5 Battery and Signal Strength Status 27 5 6 Alarms 27 5 7 View Alarm Hi...

Страница 4: ...ed service technician for repairs See Section 10 0 Support for details 3 0 Description of BBS The Cypress Envirosystems Blue Box Server BBS is a flexible industrial server that collects wireless data...

Страница 5: ...munication protocols e g OPC BACnet web services This configuration is depicted above as Option A For users who do not need to connect to an existing infrastructure the BBS can also serve as a standal...

Страница 6: ...Then connect the power cord To turn on the BBS press the rocker switch highlighted below Figure 3 BBS Power Switch Location To change the receiver channel frequency set the DIP switches accordingly Fr...

Страница 7: ...nce the web page loads the application opens to the READINGS page by default where you can find information on every data point or node in the system At the top of the READINGS page and every page in...

Страница 8: ...xample Emergency Generator or Water Inlet Pressure Reading Most recent reading taken from the node Your service representative configures the update rate when the system is installed Units Unit of mea...

Страница 9: ...hlighted in Yellow No Data This status is displayed if a Field Device has been configured on the BBS but no data has ever been sent from that field device The Row will be highlighted in gray OK This i...

Страница 10: ...ems Doc 152 10201 01 Rev 2 0 BBS User Manual Page 10 Figure 8 The Wireless Steam Trap Monitor WSTM Readings Page Figure 9 Wireless Freezer Monitor WFM Readings Page Figure 10 Wireless Battery Monitor...

Страница 11: ...he trap is building up condensate on the inlet The row is highlighted in red Out of Service There is no steam going to the trap It is not being used in the system The row is highlighted in blue Offlin...

Страница 12: ...hown in Figure 13 below It has two clearly defined sections a top section where you can add and delete individual or multiple nodes and a bottom section that displays all the nodes in the system that...

Страница 13: ...start transmitting data but the BBS must be configured to collect data for that device To add a node enter the new Node ID and press the Add button This will bring up a pop up dialog box See Figure 1...

Страница 14: ...eam Trap node Enter Node1 and Node2 that will be used to calculate the reading for new node E g Node3 Node1 Node2 Precision Precision is used to set the number of decimal places to display on the read...

Страница 15: ...ngineering reading These can be either noted down from the data sheet or the actual reading from the device E g For WTR type 0 10 V Volts1 0 Volts2 10 35 Value1 0 0001 Value2 1000 WTR One Point Calibr...

Страница 16: ...mal places will be displayed depending on how large or small the reading value is at the time Update Rate Update rate as it has been configured on the field device duration of time between samples Thi...

Страница 17: ...For WTR type 0 10 V Volts1 0 Volts2 10 35 Value1 0 0001 Value2 1000 WTR One Point Calibration Check this box if a 1 point calibration can be done This is typically used for calibrating thermocouples O...

Страница 18: ...Gauge The user will either specify the type of measurement such as PSI H2O Inch LBS or a binary type TRUE FALSE ON OFF or ACTIVE INACTIVE In case of Binary unit type the Unit column display is empty i...

Страница 19: ...y works when SMS Alarm is checked Min Alarm Threshold This is a specified lowest allowable value If the node reading drops below this number an alarm condition is created Max Alarm Threshold This is a...

Страница 20: ...t 1 2 Volts 0 Value 0 Volts 5 Value 20 2 1 High Stage Compressor Current A WFM Opt 1 2 Volts 0 Value 0 Volts 5 Value 20 3 1 Freezer Temp C or F WFM Thermocouple Type K N A N A 4 1 Door Switch Binary O...

Страница 21: ...y works when SMS Alarm is checked Min Alarm Threshold This is a specified lowest allowable value If the node reading drops below this number an alarm condition is created Max Alarm Threshold This is a...

Страница 22: ...actor that is used internally for the correction Ok Save data but keep window open Close Don t save any data just close dialog Refresh Get the latest data from the database Table 5 WFM Node configurat...

Страница 23: ...the list Orifice size Size of the orifice on the steam trap Dropdown list of user configured orifice sizes See the section on Site Settings WSTM tab Figure 26 for information on how to add or remove s...

Страница 24: ...lue the trap is considered to be leaking or blowing Outlet Temp Max out of service temperature Maximum outlet temperature where the trap is considered out of service Above this value the Max Good temp...

Страница 25: ...signed to the WSTM 5 4 2 3 1 1 Add Edit Delete Alarm Profiles To add an alarm profile from the WSTM Node Configuration Dialog screen click New and the alarm profile details will be displayed as seen i...

Страница 26: ...ter the information to the Nodeconfiguration txt file This file is a tab separated text file that lists all the configuration parameters An example file is shown in Figure 19 Use the Upload button to...

Страница 27: ...l strength of the last hop for each node Figure 20 Battery and Signal Strength Stauts 5 6 Alarms One of the benefits of Cypress Envirosystems Web Console is it immediately alerts you to potential prob...

Страница 28: ...SMTP server To use the local SMTP server select the Use Local SMPT Server for Email Alarms Check box and fill in the appropriate SMPT info Figure 21 You can change the name that appears in the right...

Страница 29: ...the last two hours for all nodes You can specify the time period and the nodes that you want to see an alarm history for by using the dialog box at the top of the page as shown in Figure 23 Figure 23...

Страница 30: ...ge in the Main Menu This displays the Alarm History page A green Alarm Reset button is located at the top of this page 2 Click the green Alarm Reset button This will take you to the Alarm Reset page 3...

Страница 31: ...er names in the WSTM Readings tab For all the dropdown menus in the WSTM Node configuration dialog the user can modify the entries from the WSTM Categories window on the WSTM Settings tab as seen in F...

Страница 32: ...de the United States Command Function CYWGR AS SiteID NodeID Find Node status for specified NodeID CYWGR TR SiteID NodeID Get Node reading for specified NodeID CYWGR AR SiteID NodeID Reset Alarm for s...

Страница 33: ...ale uncheck the checkbox and the Min and Max fields will enable Min If Auto Scale is turned off the user must specify the min Y value on the graph Max If Auto Scale is turned off the user must specify...

Страница 34: ...n the graph click on a point The node ID number the timestamp and the value display on the top left corner of the graph 5 10 3 Zoom To zoom hold down the left click button on a point and drag the poin...

Страница 35: ...cify the node IDs you want to display You can select nodes individually using the List of Nodes drop down list or enter the node ID number manually or check the box next to Select All Nodes If you sel...

Страница 36: ...2 Reports An executive summary is available for WSTMs which gives an overall status of all the steam traps that are currently being monitored An energy summary is calculated which shows amount of stea...

Страница 37: ...configure the firewall as needed 8 0 Troubleshooting I get an error message when I try and enter an email address into the SMS Alert Phone number is a required field If you do not enter a phone numbe...

Страница 38: ...optional encryption and minimal interference with existing wireless systems for additional details please see FAQ at www cypressenvirosystems com Approvals FCC Class B compliant RoHS ETSI compliant Po...

Отзывы: