background image

 

Output Relay Rating 

Max 

Voltage 

Current 

30VDC/125VAC 

3A (per relay) 

 
 

Function Description 

NO/NC 

Jumper 

Position 

Status 

Condition

 

JP1

NO 

PIN 1 short to PIN 5 

Activated on 

UPS Fault

 

(Inverter Fault / DC Bus Fault / Over Temperature 
/ Bat Test Fail / Bat Over Charge / Fan Error) 

T8 short to T9/T10 

JP1

NC 

PIN 1 open to PIN 5 

T8 open to T9/T10 

JP2

NO 

PIN 2 short to PIN 5  Activated on 

Summary alarm

 

(Inverter  Fault  /  Output  Short  /  DC  Bus  Fault  / 
Over Temperature / Over Load / Bat Over Charge 
/ Battery Low / Bat Test Fail / Wiring Fault / Load 
Over Setting Level / Fan Error) 

                                               

T3 short to T9/T10 

JP2

NC 

PIN 2 open to PIN 5 

T3 open to T9/T10 

N/A 

PIN 6 short to PIN 5 

Activated when 

UPS is OFF or in Bypass Mode

 

T4 short to T9/T10 

JP3

NO 

PIN 7 short to PIN 5 

Activated when 

Battery Low

 

T5 short to T9/T10 

JP3

NC 

PIN 7 open to PIN 5 

T5 open to T9/T10 

N/A 

PIN 8 short to PIN 5 

UPS is on 

T7 short to T9/T10 

JP4

NO 

PIN 9 short to PIN 5 

Activated when 

Utility Power Fails

 

T6 short to T9/T10 

JP4

NC 

PIN 9 open to PIN 5 

T5 open to T9/T10 

 

Example Application 

Provide 12VDC from 

COMMON

(PIN 5/T9/T10) to 

GND

(PIN 3/T2). 

1.

 

Remote  Monitor

Install  alerting  mechanism  from  DB-9  port/ 

Terminal(PIN 1/T8, PIN 2/T3, PIN 6/T4, PIN 7/T5, PIN 8/T7, PIN 9/T6) 
to 

GND

(PIN 3/T2).   

2.

 

Remote  Shutdown

Install  a  push  button  from 

COMMON             

(PIN  5/T9/T10)  to 

REMOTE  SHUTDOWN

(PIN  4/T1).  Press  the 

button for at least 5 seconds to shut off the UPS remotely.   

Note:  When  the  UPS  is  in  battery  mode,  the  shutdown  pins               
(PIN  4  &  PIN  3)  require  a  minimum  of  5  seconds  of  high  level  signal 
(connection to +12VDC) to perform the UPS shutdown where output is 
turned off after 120 seconds.

 

1

6

2

7

3

4

5

8

9

UPS FAIL

SUMMARY ALARM

GND (Common for PIN 4)

REMOTE SHUTDOWN

COMMON (For Relays)

BYPASS / UPS OFF

BATTERY LOW

UPS ON

POWER FAIL

12V

 

 

Conformance Approvals 

FCC Warning 

This equipment has been tested and found to comply with the limits for a Class 
B digital device, pursuant to part 15 of the FCC Rules. These limits are designed 
to  provide  reasonable  protection  against  harmful  interference  in  a  residential 
installation.  This  equipment  generates,  uses  and  can  radiate  radio  frequency 
energy  and,  if  not  installed  and  used  in  accordance  with  the  instructions,  may 
cause  harmful  interference  to  radio  communications.  However,  there  is  no 
guarantee  that  interference  will  not  occur  in  a  particular  installation.  If  this 
equipment does not cause harmful interference to radio or television reception, 
which  can  be  determined  by  turning  the  equipment  off  and  on,  the  user  is 
encouraged  to  try  to  correct  the  interference  by  one  or  more  of  the  following 
measures: 
- Reorient or relocate the receiving antenna. 
- Increase the separation between the equipment and receiver. 
- Connect the equipment into an outlet on a circuit different from that to which 

the receiver is connected. 

- Consult the dealer or an experienced radio/TV technician for help. 

 

This  device  compiles with Part 15  of the FCC  Rules.  Operation  is  subject  to the 
following  two  conditions:  (1)  this  device  may  not  cause  harmful  interference, 
and (2) this device must accept any interference received, including interference 
that may cause undesired operation. 
 
NOTE:  THE  MANUFACTURER  IS  NOT  RESPONSIBLE  FOR  ANY  RADIO  OR  TV 
INTERFERENCE  CAUSED  BY  UNAUTHORIZED  TO  THIS  EQUIPMENT.  SUCH 
MODIFICATIONS  COULD  VOID  THE  USER’S  AUTHORITY  TO  OPERATE  THE 
EQUIPMENT. 
 

Canadian Compliance Statement 

This  device  complies  with  Industry  Canada  license-exempt  RSS  standard(s). 
Operation  is  subject  to  the  following  two  conditions:  (1)  this  device  may  not 
cause  interference,  and  (2)  this  device  must  accept  any  interference,  including 
interference that may cause undesired operation of the device. 
 
Le  présent  appareil  est  conforme  aux  CNR  d'Industrie  Canada  applicable  aux 
appareils  radio  exempts  de  licence.  L'exploitation  est  autorisée  aux  deux 
conditions  suivantes  :  (1)  l'appareil  ne  doit  pas  produire  de  brouillage,  et  (2) 
l'appareil  doit  accepter  tout  brouillage  radioélectrique  subi,  même  si  le 
brouillage est susceptible d'en compromettre le fonctionnement. 
CAN ICES-3 (B)/NMB-3(B) 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CyberPower Technical Support 

Phone: 1-877-297-6937 

Email: [email protected] 

Web: www.CPSww.com 

Mail: 4241 12th Avenue E, Suite 400 Shakopee, MN 55379

 

 

Hours of Operation: 

Monday – Friday, 7:00am – 6:00pm (CST) 

 

Entire contents copyright © 2015 CyberPower Systems, Inc. 

All rights reserved. Reproduction in whole or in part without permission is 

prohibited.

 

 

Отзывы: