background image

Relay Control Card

RELAYIO500

 

 

 
 
 
 
 

 
 
 
 
 
 
 

 

 
 

Relay Control Card 

RELAYIO500 

 

User’s Manual 

 

 

K01-0000416-01 

Internal Circuit 

 

 

RELAYIO500 Card Pinout 

Pin 

Assignment 

Function 

I/O 

Pin1 

UPS FAULT 

O/P 

Pin2 

SUMMARY ALARM 

O/P 

Pin3 

GND (Common for Pin4) 

Power GND 

Pin4 

REMOTE SHUTDOWN 

Power + Vcc 

Pin5 

COMMON (For Relays) 

O/P 

Pin6 

BYPASS

 1

 / UPS OFF 

O/P 

Pin7 

BATTERY LOW 

O/P 

Pin8 

UPS ON 

O/P 

Pin9 

UTILITY LINE FAIL 

O/P 

Note: All relay contacts are normally open (N.O.) except for Pin6. 
          Acceptable Power + Vcc for Pin4 is 7.5 – 12V, 0.0672W Max. 

1

 For OL series UPS models only 

 
 
 

 

1

6

2

7

3

4

5

8

9

UPS FAULT

SUMMARY ALARM

GND (Common for Pin4)

REMOTE SHUTDOWN

COMMON (For Relays)

BYPASS

1

 / UPS OFF

BATTERY LOW

UPS ON

UTILITY LINE FAIL

 

GND

Overview 

The CyberPower Relay Control Card (RELAYIO500) offers users the 
solution for UPS status monitoring via 5 output relays. In addition, the 
RELAYIO500 card provides 1 input contact to perform UPS shutdown in 
battery mode. This card is compatible with most CyberPower UPS devices 
with expansion slot. 

 

Installation Guide 

The RELAYIO500 card is hot-swappable and can be installed while the 
UPS is on. 
1. Remove the two retaining screws on the expansion slot cover, and then 

remove the cover. 

2. Install the CyberPower RELAYIO500 card into the expansion slot. 
3. Re-install and tighten the retaining screws. 
 

Technical Specifications 

RELAYIO500 

Electrical 

External S/D Voltage 

7.5V – 12V 

Power Dissipation 

1.35W Max 

(Default 12V input) 

Physical 

Dimensions (WxHxD) 

41.8 x 14.2 x 81mm 

(1.65 x 0.6 x 3.2 in) 

Weight 

52g (1.92oz) 

Environmental 

Operating Temperature 

0°C – 40°C (32°F - 104°F) 

Operating Humidity 

0% – 95% (Non-condensing) 

 

Output Relay Rating 

Maximum 

Voltage 

Current 

30VDC / 125VAC 

3A (per relay) 

 
 

 

Function Description 

Status 

Condition 

Pin1 short to Pin5 

UPS fault (Inverter Fault / DC Bus Fault / Over 
Temperature / Output Short / Battery Over Charge / 
Battery Test Fail

 1

 / Fan Error

 1 

Pin2 short to Pin5 

Summary alarm (Inverter Fault / DC Bus Fault / 
Output Short / Over Temperature / Over Load / 
Battery Missing / Battery Over Charge / Battery Low / 
Wiring Fault / Runtime Low

 2

 / Battery Test Fail

 1

 / 

Load Over Setting Level

 1

 / Fan Error

 1 

Pin6 short to Pin5 

UPS is OFF. / UPS is in Bypass Mode.

 1

 

Pin7 short to Pin5 

Battery Low 

Pin8 short to Pin5 

UPS is on. 

Pin9 short to Pin5 

Utility Line Fail 

1

 For OL series UPS models only 

2

 For PR/OR series UPS models only 

 

Example Application 

Supply 12VDC to the COMMON contact and connect LEDs to the DB-9 
port pins 1, 2 and 6 to 9. Connect a push button to COMMON (Pin5) and 
REMOTE SHUTDOWN (Pin4). Pressing the button for at least 5 seconds 
will shutdown the UPS when it is on battery. 
Note: When the UPS is on battery, the REMOTE SHUTDOWN input (Pin4 
& Pin3) accepts at least 5 seconds of high level signal (+12VDC) to perform 
the UPS shutdown. UPS output power will turn off after 120 seconds. 

 

 

 

 

1

6

2

7

3

4

5

8

9

UPS FAULT

SUMMARY ALARM

GND (Common for Pin4)

REMOTE SHUTDOWN

COMMON (For Relays)

BYPASS

1

 / UPS OFF

BATTERY LOW

UPS ON

UTILITY LINE FAIL

12V

Отзывы: