1. General Mode:
a.
Press the “Display-Toggle” button to check the status of the UPS status:
b.
Press and hold the “Display-Toggle” button for 4 seconds,
If the machine is in the Battery Mode with active alarm, it will become silent.
If the machine is in the Line Mode, a self- diagnostic test will take place.
c.
If the “Display-Toggle” button remains untouched for over 30 seconds, the LCD backlight will turn off
automatically.
2. Set-up Mode
Step 1:
Hold the “Display-Toggle” button for 10 seconds to enter the UPS Set-Up Mode.
Step 2:
By pressing the Display toggle, users can switch between setup functions. Some User Configurable
functions are as follows:
a.
Delay Time: The time delay between switching from Battery Mode to Line Mode. There are 9 different
settings. The default setting is 0 minutes.
b.
Battery Pack Numbers: This function provides the estimated UPS runtime using various numbers of
battery packs. The default setting is 0.
c.
Static Frequency Tolerance: There are 6 settings (1,2,4,6,8,10 %), and the default setting is +/-6%.
Functional description: The setting may be adjusted to the quality of the electricity in use.
d.
Slew rate: Also known as Dynamic Frequency Tolerance. There are 5 different settings (0.25,0.5,1,2,4
Hz/Sec). The fault value is 4Hz/sec. Functional Description: “Slew Rate” indicates the tolerance of a
device in accepting frequency variance. Lower “Slew Rate” results in less tolerance but better protection
for the connected load and vice versa.
e.
Low Battery Shutdown Voltage: This function will adjust the UPS shutdown point according to the
battery’s remaining capacity.
These programmable items are sorted by unit as in the following table
:
Step 3:
Press and hold the display-toggle for 4 seconds. When the icons blink, the value of each item is
changed by slightly pressing the toggle.
Item
Unit
1
Input Voltage
V
2
Output Voltage
V
3
Output Frequency
Hz
4
Load
Kw
5
Estimate Run Time
Min
6
Load Capacity
%
7
Battery Capacity
%
8
Centigrade
℃
9
Fahrenheit
℉
Items
Unit
Delay Time
Min
Battery Pack Numbers
A
Voltage Mode (220/230/240)
V
Static Frequency Tolerance
%
Slew Rate
Hz
Low Battery Shutdown Voltage
V
Firmware Version
None
LCD SETUP FUCTIONS