LCD SETUP FUNCTIONS
11
Configure Submenu
Available Settings
Default Setting
Output Voltage
= [100V] [110V] [115V] [120V] [125V]
1
= [200V] [208V] [220V] [230V] [240V]
120V
208V
Sync Freq Window
Range= [+/- 1%] [+/- 2%] [+/- 3%] [+/- 4%] [+/- 5%]
[+/- 6%] [+/- 7%] [+/- 8%] [+/- 9%] [+/-10%]
+/- 5%
Bypass V Window
Range= [+10%/-10%] [+10%/-15%] [+10%/-20%]
[+15%/-10%] [+15%/-15%] [+15%/-20%]
+10%/-15%
Bypass Condition
[Check Freq/Volt] [Check Volt Only] [No Bypass]
Check Freq/Volt
ECO Mode
2
[Disable] [Enable]
Disable
[V Range= +/-15%] [V Range= +/-10%] (for [Enable])
V Range= +/-10%
Manual Bypass
[Disable] [Enable]
Disable
UPS Diagnostic
[Battery Test] [Alarm Test] [Indicator Test] [Fan Test]
[Battery Test]
[Activate?]
None
Audible Alarms
[Disable] [Enable]
Enable
EBM Number
= [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]
0
Wiring Fault
[Disable] [Enable]
Disable
NCL Control
[Outlet On] [Outlet Off]
Outlet On
Language
[English] [Español-Spanish] [Fran
ç
ais-French] [Deutsch-German]
English
Generator Mode
3
[Disable] [Enable]
Disable
Communication
[Disable] [Enable]
Enable
Dry Relay Set
[I/P Power Fail] [Battery Low] [Summary Alarm]
[UPS On Bypass] [UPS Fail]
I/P Power Fail
Converter Mode
4
[Converter Off] [O/P Freq = 50Hz] [O/P Freq = 60Hz]
Converter OFF
Screen Saver
[Disable] [1 Minutes] [5 Minutes]
5 minutes
Clear Event Log
[Activate?]
None
Button OFF LOCK
[Disable] [Enable]
Disable
Charger Function
[SBM] [Constant]
SBM
Signal Inputs
[Disable] [EPO] [ROO]
Disable
Charger Check
[Disable] [Enable]
Disable
Reset ReplaceBAT
[Activate?]
None
IP Address
[Mode:DHCP] [Mode:Manual]
Mode:DHCP
[IP Address] [Subnet Mask] [Gateway] (for [Mode:Manual])
None
Reset LoadEnergy
[Activate?]
None
1
For OL1500/2200/3000RTXL2U, 100V is derated by 20%, 110/115V is derated by 10%
Output voltage default setting varies by country.
2
This function
can’t be set when Manual Bypass, Generator Mode or Converter Mode is enabled.
3
UPS has no bypass when Generator Mode is enabled.
4
UPS has no bypass when Converter Mode is enabled. This function can only be set before the UPS is on.