LCD SETUP FUNCTIONS
16
Configure Submenu
Available Settings
Default Setting
Output Voltage
= [200V] [208V] [220V] [230V] [240V]
230V*
Sync Freq Window
Range= [+/- 1%] [+/- 2%] [+/- 3%] [+/- 4%] [+/- 5%]
[+/- 6%] [+/- 7%] [+/- 8%] [+/- 9%] [+/-10%]
+/- 5%
Bypass V Window
Range= [+10%/-10%] [+10%/-15%] [+10%/-20%]
[+15%/-10%] [+15%/-15%] [+15%/-20%]
+10%/-15%
Bypass Condition
[Check Freq/Volt] [Check Volt Only] [No Bypass]
Check Freq/Volt
ECO Mode**
[Disable] [Enable]
Disable
[V Range= +/-15%] [V Range= +/-10%] (for [Enable])
V Range= +/-10%
Manual Bypass
[Disable] [Enable]
Disable
Battery Test
[Activate?]
None
Audible Alarms
[Disable] [Enable]
Enable
EBM Number
= [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]
0
Wiring Fault
[Disable] [Enable]
Disable
Language
[English] [Español-Spanish] [Fran
ç
ais-French] [Deutsch-German]
English
Generator Mode***
[Disable] [Enable]
Disable
Communication
[Disable] [Enable]
Enable
Dry Relay Set
[I/P Power Fail] [Battery Low] [Summary Alarm][UPS On Bypass] [UPS Fail]
I/P Power Fail
Converter Mode****
[Converter Off] [O/P Freq = 50Hz] [O/P Freq = 60Hz]
Converter OFF
Screen Saver
[Disable] [1 Minutes] [5 Minutes]
5 minutes
Clear Event Log
[Activate?]
None
Button OFF LOCK
[Disable] [Enable]
Disable
Charger Function
[SBM] [Constant]
SBM
Signal Inputs
[Disable] [EPO][ROO]
Disable
Charger Check
[Disable] [Enable]
Disable
With Transformer
[Disable] [Enable]
Disable
Backfeed Check
[Disable] [Enable]
Disable
*) Output voltage default setting depends on different nation or order requested.
**) This function
can’t be set when Manual Bypass, Generator Mode or Converter Mode is enabled.
***) UPS has no bypass when Generator Mode is enabled.
****) UPS has no bypass when Converter Mode is enabled. This function can only be set before the UPS is on.
SILENCING AUDIBLE ALARMS
1.
Press any of four function buttons on the LCD module; Note: the alarm can not be turned off for a
“
Battery Low
”
condition. This condition will still result in an audible alarm.
2.
Configure
“
Audible Alarms
” as “
Disable
” on the LCD module and it will stop warning of any malfunction audibly.
MANUAL BATTERY TEST
Configure
“
Battery Test
” as “
Active
” on the LCD module; and it will perform the “
Manual Battery Test
”