TECHNICAL SPECIFICATIONS
DEFINITIONS FOR ILLUMINATED LED INDICATORS
LED
Alarm
Condition
On Off
Normal
Flash
Beep Twice
Utility Failure - The UPS is providing battery power to outlets.
Flash
Rapid
Beeping
Utility Failure - The UPS is providing battery power. The rapid beeps indicate
the battery will run out of power shortly.
On/Flash
Constant
Tone
Overload - Occurs when connected equipment exceeds the rating of the unit.
Turn the UPS off and unplug at least one piece of equipment from the UPS.
TROUBLESHOOTING
Problem
Possible Cause
Solution
The UPS does not perform
expected runtime.
Batteries are not fully charged.
Recharge the battery by leaving the
UPS plugged in.
Battery is slightly worn out.
Contact CyberPower Systems
Technical Support.
The UPS will not turn on.
The unit is not connected to an AC
outlet.
The unit must be connected to a
220-240V outlet.
The battery is worn out.
Contact CyberPower Systems
Technical Support.
Mechanical problem.
Contact CyberPower Systems
Technical Support.
Outlets do not provide power to
equipment
Fuse is blown or breaker is tripped
due to overload.
Turn the UPS off and unplug at least
one piece connected equipment.
Unplug the power cord of the UPS then
replace the blown fuse with a spare
one or press the circuit breaker knob.
Connect power cord then turn the UPS
on. Make sure that your spare fuse
meets the specification.
Batteries are discharged
Allow the unit to recharge for at least 4
hours.
Unit has been damaged by a surge or
spike.
Contact CyberPower Systems
Technical Support.
For more information, visit
www.cpsww.com
All rights reserved. Reproduction without permission is prohibited.
Model
BU600E-AS
BU1000E-AS
Capacity (VA)
600 1000
Input
Voltage Range
140~300Vac
Nominal Frequency
50 Hz
Output
On Battery Output Voltage
Simulated Sine Wave at /-5%
On Battery Output Frequency
50 Hz +/-1%
Overload Protection
Breaker / Fuse
Physical
Total # of UPS Receptacles
3 4
Dimensions (H x W x D)(mm)
91.5 x 158 x 240
110.5 x 190 x 290
Weight
3.8 kg
6.9 kg
Battery
Sealed Maintenance Free Lead Acid
Battery
RBP0043 x1
RBP0046 x2
Typical Recharge Time
8 Hours
Warning Diagnostics
Indicators
Power On / Using Battery
Audible Alarms
On Battery, Low Battery, Overload, Fault
Environmental
Operating Temperature
0
°
C to 40
°
C
Operating Relative Humidity
0 to 90%
Management
Auto-Charger
Yes
Auto-Restart
Yes