4
Copyright © 2013 CyberPower Systems, Inc.
Step2: Connect the External Battery Pack (s)
One Battery Pack
Connect the Battery Pack’s output cord into the UPS’s input port.
Ensure the color coded Battery Pack connector lines up correctly with the colors in the
UPS socket.
Multiple Batteries Packs
When connecting multiple Battery Packs, simply use the available socket(s) on the
Battery Packs to add additional packs. All battery pack module must connect in right
type, red to red, black to black, green to green.
When connecting with numerous battery packs to extend the battery runtime, link the
output plugs of all except the one that connects to the UPS.
CAUTION!
Single AC inlet could only support ten battery packs on limited. If users
connect more than ten battery packs, plug more wall receptacle to avoid overload.
CAUTION!
Do not disconnect the battery pack when UPS is operating.
CAUTION!
Do not connect the battery pack into itself.
CAUTION!
Additional battery packs are to be connected in parallel connected, the
voltage maintains the same, yet the battery amp-hour capacity depends on the
numbers of battery packs in the set up.
CAUTION!
For GROUND protection, plug AC power connectivity to wall receptacle
with ground line before using battery pack.