Chapter 2 Installation Instruction
22
HSTP3T 10-40 KE/KEBC/KEBCWOB User Manual
Remote EPO Input Port
J4 is the input port for remote EPO. It requires shorting NC and +24V and disconnecting
NO and +24V during normal operation, and the EPO is triggered when opening NC and +24V
or shorting the NO and +24V. The port diagram is shown in Fig.2-16, and port description is
shown in Table 2.7.
E
P
O
_
N
C
+
2
4
V
+24V
J4
EPO_NO
+24V
+24V
+24V
Fig.2-16 Diagram of input port for remote EPO
Table 2.7 Description of input port for remote EPO
Port
Name
Function
J4-1
REMOTE_EPO_NC
Trigger EPO when disconnect with J4-2
J4-2
+24V_DRY
+24V
J4-3
+24V_DRY
+24V
J4-4
REMOTE_EPO_NO
Trigger EPO when connect with J4-3
Generator Input Dry Contact
The default function of J5 is the interface for generator J5 Connect pin 2 of J5 with +24V
power supply; it indicates that the generator has been connected with the system. The
interface diagram is shown in Fig.2-17, and interface description is shown in Table 2.8.
J5
GEN
+24V
AUX-N.O.
AUX-N.O.
Generator
Fig.2-17 Diagram of status interface and connection of generator
Table 2.8 Description of status interface and connection of generator
Port
Name
Function
J5-1
+24V_DRY
+24V
J5-2
GEN_CONNECTED
Connection status of generator
J5-3
GND_DRY
Power ground for +24V
Содержание HSTP3T10KE