background image

16 

 

 

6 TECHNICAL SPECIFICATIONS 

 

Model   

CPS1000EILCD 

CPS1200EILCD 

CPS2200EILCD 

Power Rating (VA/Watt) 

1000VA/680W 

1200VA/780W 

2200VA/1320W 

Input 

Input Voltage Range 

Narrow Mode: 190 - 260Vac                                                                                                                                                                                                             

Wide Mode: 100 - 280Vac 

Input Frequency 

50/60Hz (Auto-sensing) 

Output 

Output Voltage 

230Vac 

Output Frequency   

50/60Hz   

Outlet Type 

(1) UN 

(1) UN 

(1) UN 

Transfer Time 

< 8ms (Typical Narrow Mode) 

Battery 

Battery Voltage 

12V 

24V   

24V 

Charging Current 

20A 

20A 

15A 

Environmental 

Operating Temperature (°C) 

0

C to 40

Operating Relative Humidity 

0 to 90% (non-condensing) 

Physical 

Dimensions (WxHxD) (mm.) 

250 x 90 x 265 

250 x 90 x 265 

250 x 90 x 265 

Weight (kg.) 

2.05 

2.2 

2.2 

 

For more information, visit 

www.cyberpower.com

 

All rights reserved. Reproduction without permission is prohibited.

 

 

 

 

 

Содержание CPS1000EILCD

Страница 1: ...Power Inverter CPS1000EILCD CPS1200EILCD CPS2200EILCD User s Manual ...

Страница 2: ...2 ...

Страница 3: ...ower Requirements of Your Equipment 7 2 4 Hardware Installation Guide 7 3 DEFINITIONS FOR ILLUMINATED LCD INDICATORS 9 4 OPERATION CONFIGURATION 11 Power On Off 11 Function Setup 11 Audible Alarm 11 Function Setup Guide 11 Charger Control 13 Input Voltage Range Selector 13 5 TROUBLESHOOTING 14 6 TECHNICAL SPECIFICATIONS 16 ...

Страница 4: ...vent accumulation and concentration of hydrogen gas at the top of the compartment CAUTION A battery can present a risk of electrical shock and high short circuit current When working on batteries remove watches rings or other metal objects Use tools with insulated handles CAUTION Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected CAUTION To avo...

Страница 5: ... home office users the always on power supply with the exceptional power performance Featuring the high efficiency conversion design the Power Inverter supplies long lasting and reliable power to various appliances and provide longer backup for equipment These units can be installed in either a horizontal or wall mounted placement to make the most of your space Power Inverter Input Power Cord User...

Страница 6: ...6 CPS1000EILCD CPS1200EILCD CPS2200EILCD Application Diagram ...

Страница 7: ...m performance keep the load below 80 of the unit s rated capacity 2 4 Hardware Installation Guide Step 1 Connect the Battery For optimal battery life and reasonable recharging time make sure the batteries capacity no less than 100Ah Use batteries with same brand type and capacity Connect DC input cables of this product to external batteries Red cable to the battery s Positive polarity Black cable ...

Страница 8: ...s achieved To recharge the battery and maintain optimal battery charge simply leave the unit plugged into a wall outlet at all times The battery can be charged whether the unit is turned on or off DO NOT connect Neutral of the Power Distribution Box to a the OUTPUT Neutral of this product or b the INPUT Neutral of connected equipment Otherwise reversed polarity will damage the product and connecte...

Страница 9: ...mation Icon Description Normal Mode Power On The Power Inverter is turned on Standby Mode Power Off The Power Inverter is off while the LCD display remains on Utility Power Utility power source supplies AC power Load Capacity The approximate load capacity of the unit s outlet in 25 increments Battery Capacity The approximate battery capacity and charging status in 25 increments Fault This icon app...

Страница 10: ...pes of modes regarding to the operation of the Power Inverter The corresbonding LCD displays are as shown below LCD Display Operation Mode Standby Mode In Standby Mode the Power Inverter is off and the Utility power bypasses to output and in the meantime charges the battery The LCD is on to show battery status Line Mode The Power Inverter is turned on and AC input power is normal It supplies power...

Страница 11: ...is selected short press SETUP button to confirm the setting The unit will leave Setup Mode if there is no operation in 60 seconds Audible Alarm Press SELECT button for 2 seconds to enable the audible alarm beeps once or disable beeps twice the audible alarm The MUTE icon will appear on the LCD display when the audible alarm is disabled Function Setup Guide Function Options Default Description Page...

Страница 12: ... Page 4 LCD Auto Sleep Off 0 5 1 2 Min ESC 1 Min If Auto Sleep is selected the LCD display will shut off after 0 5 1 2 minutes if no activity Page 5 Cycling Display Off 0 5 1 Min ESC 0 5 Min If the buttons are not touched in 0 5 1 minute the LCD will start cycling the Inverter information Page 6 Back to Default ESC Yes ESC Select Yes to restore the factory default settings Page 7 Return to Status ...

Страница 13: ...Voltage Range Selector Input voltage range is defined in specification section Output voltage is the same as input voltage in AC mode Narrow 190 260Vac For connected equipment that are sensitive to the fluctuation of voltage range narrow the input voltage range and the output voltage will follow Wide 100 280Vac For connected equipment that are less sensitive to the fluctuation of voltage range set...

Страница 14: ...rvicing of the DC fuse should only be performed by trained personnel For more information on DC fuse replacement contact CyberPower Systems Batteries are discharged Recharge the unit for at least 8 hours The product may require service Contact CyberPower Systems There is no LCD display The product is not turned on Press the power button Batteries are discharged Recharge the unit for at least 8 hou...

Страница 15: ...e Alarm A64 Overload Rapid beeping every 1 2 second E07 Output Voltage High Constant tone E09 Output Short Constant tone E14 Overload Fault Constant tone E18 Fan Fail Constant tone E13 Over Charge Constant tone E25 Output Unbalance Constant tone ...

Страница 16: ...ac Output Frequency 50 60Hz Outlet Type 1 UN 1 UN 1 UN Transfer Time 8ms Typical Narrow Mode Battery Battery Voltage 12V 24V 24V Charging Current 20A 20A 15A Environmental Operating Temperature C 0 C to 40 C Operating Relative Humidity 0 to 90 non condensing Physical Dimensions WxHxD mm 250 x 90 x 265 250 x 90 x 265 250 x 90 x 265 Weight kg 2 05 2 2 2 2 For more information visit www cyberpower co...

Страница 17: ......

Отзывы: