background image

I.L. 15579B

Page 3

Effective 12/98

torque loading.  Torque values for line/load terminals
are given in Tables 2.1 and 2.2 and on the MCP name-
plate.

3-0  MANUAL OPERATION

The MCP is manually operated by the handle or the
PUSH-TO-TRIP button.  The MCP handle has three
indicating positions, two of which are shown with handle
lettering to indicate ON and OFF.  Trip status is indicat-
ed by white strip on handle.

Circuit Breaker Reset

After tripping, the MCP is reset by moving the MCP han-
dle to the extreme OFF position.

PUSH-TO-TRIP Button

The PUSH-TO-TRIP button checks the tripping function
and is used to periodically exercise the operating mech-
anism.  The button is designed to be operated by using
a small screwdriver.

Adjustment of Trip Setting

The trip setting adjusting mechanism permits the MCP
to be fine tuned to provide more precise protection.  The
mechanism consists of a cam with six positions for dif-
ferent trip levels.  The trip levels are labeled A through
F; actual trip values are shown on the MCP cover name-
plate and in Tables 3.1.  Adjustments is made only in
one direction as indicated in Figure 3-1.  A rotation stop

prevents the adjustment wheel from being rotated
against indicated adjustment direction.  The MCP can
be damaged  if adjustment is forced against indicated
adjustment direction.  Once the F setting has been
reached, continue adjusting in the same direction to
return to the A setting.  To adjust the trip level, perform
the following steps:

3-1. Determine the motor full load current from the
motor nameplate.  Refer to Table 3.1 and select appro-
priate MCP trip setting.  Using a small screwdriver,
rotate wheel in direction indicated (See Figure 3-1) to
the appropriate setting.

3-2. For closest protection, turn the adjustment wheel to
successively lower settings until the MCP trips when the
motor is started.  Only adjust in direction indicated (See
Figure 3-1).  When this setting has been determined,
turn the adjustment wheel to the next highest setting.
The MCP is now adjusted for normal operation.

3-3.  If the MCP does not trip at the lowest setting (A),
leave the adjustment wheel at this position.

4-0  INSPECTION AND FIELD TESTING

G-Frame MCPs are designed to provide years of almost
maintenance-free operation.  The following procedure
describes how to inspect and test a MCP in service.

Inspection

MCPs in service should be inspected periodically.  The
inspection should include the following checks:

Circuit Terminal

Screw

Wire 

AWG 

Wire Metric

Breaker

Type

Head

Type Range

Wire 

Amps.

Material

Type

Range (mm

2

)

3-20

Clamp

Slotted

Cu/Al

#14-10

1.5-4

(Plated Steel)

25-63

Pressure

Slotted Cu/Al

#10-1/0

4-50

(Aluminum Body)

Not UL Listed sizes.

Table 2.1  Terminal Types
For line and load-side.  Terminals are UL Listed as suit-
able for wire type and size given below.

AWG Wire

Torque 

Torque

Range

Value lb-in

Value N.m.

#14-10

20

2.26

#8

40

4.52

#6-1/0

45

5.09

Table 2.2  Terminal Torque Values

Figure 3-1  MCP Manual Controls 

Handle

Trip Indicator:
White Color
When Tripped

ON

TRIP

OFF
RESET

Push to Trip
Button

Trip Setting
Adjustment Mechanism
Adjust Only In
Direction Shown By
Arrow

Отзывы: