Effective October, 2000
Page 12
Connect the ring terminals of the Sensor
Harness to the Sensor Terminals. Refer to
Section 12 of the Retrofit Application Data,
supplied with the Retrofit Kit, for detailed wiring
specifications.
Depending on the Sensors supplied with the
Retrofit Kit, the following conventions apply.
Sensor Style No.
8256A98H01
X1-X2
=
2000A
4A35733H01
X1-X3
=
1600A
X1-X2
=
800A
4A35734H01
X1-X3
=
800A
X1-X2
=
400A
X1 - White, X2 - Black, X3 - Red
For Kits Supplied with a PT Module Only.
Refer to Section 7-3, Power Flow Convention, of
the Retrofit Application Data, supplied with the
Retrofit Kit, for additional wiring information and to
verify the Phase Convention used on this Breaker
Application.
C. Install the supplied grommet in the hole near
the top right corner of the Breaker Back Plate.
D. Route the Sensor Harness towards the right
rear of the Breaker, then up along the inside of
the Breaker and through the grommet just
installed.
E. Route the Sensor Harness along the right rear
of the Breaker Back Plate down to the Sensors.
Connect the ring terminals of the Sensor
Harness to the 3-Point Sensor Terminal Blocks.
Refer to Section 12 of the Retrofit Application
Data, supplied with the Retrofit Kit, for detailed
wiring specifications.
Depending on the Sensors supplied with the
Retrofit Kit, the following conventions apply.
Sensor Style No.
4A35733H01
X1-X3
=
1600A
X1-X2
=
800A
4A35734H01
X1-X3
=
800A
X1-X2
=
400A