AC/DC MODELS

AC/DC MODELS

DC-ONLY MODELS

(AC Operation)

(DC Operation)

Input Voltage

20 to 264 V ac, 50/60 Hz

15 to 30 V dc

10 to 30 V dc

(15 to 24 V dc above 55° C/131° F)

(10 to 24 V dc above 55°C/131° F)

Power Dissipation

1.5 W maximum

1.5 W maximum

1 W maximum

Output Type

VMOS (bi-directional)

NPN (sink)

NPN and PNP (dual outputs)

Current Switching

300 mA maximum

300 mA maximum

PNP (source): 100 mA maximum;

Capacity

NPN (sink): 250 mA max.
(120 mA max. above 55° C/131° F)

Voltage Switching

375 V peak maximum

375 V peak maximum

30 VDC maximum

Capacity

Off-State Leakage

250

 µ

A typical

250 

µ

A typical

10 

µ

A maximum

500 

µ

A maximum

500 

µ

A maximum

Surge Current

2 A maximum

2 A maximum

1 A maximum

On-State Voltage

- - -

1.8 V at 10 mA; 3.5 V at 300 mA

NPN: 400 mV at 10 mA,

Drop

          1.5 V at 250 mA;
PNP:  2.8 V at 100 mA

Response Time

8 mS

3.5 mS

Short Circuit

Sensor will turn off immediately when a short or overload is detected (Indicator LED will flash).

Protection

Turn power OFF and back ON to reset.
IMPORTANT:  During installation, correct power connections must be made first to ensure fail-safe short
circuit protection of the outputs.

Light/Dark Operation Switch selectable on detector

Temperature Range

Operating and Storage; Source: -20° to +70° C (-4° to +158° F); Detector: -40° to +70° C (-40° to +158° F)

Material of

Lens: Polycarbonate; Cable jacket: PVC; Body: Structural polyurethane foam

Construction

(do not expose to concentrated acids, alcohols, or ketones)

Cable/Connector

6-foot cable, 3-wire (ac/dc models), 4-wire (dc-only models); Micro Connector, 4-pin male

Vibration and Shock

Vibration: 30 g over 10 Hz to 2 kHz; Shock: 100 g for 3 mS 1/2 sinewave pulse

Indicator LED

Source: Lights when power is ON; Detector: Lights steady when output is ON, Flashes when short circuit
protection is in latch condition

Sunlight Immunity

10,000 foot-candles

Enclosure Ratings

NEMA 1, 2, 3, 4, 4X, 6, 12, and 13
(Our products conform to NEMA tests as indicated, however, some severe washdown applications can
exceed these NEMA test specifications.If you have questions about a specific application, contact our
Applications Department.)

Approvals

Contact factory for the latest list of approvals

SPECIFICATIONS

Содержание 11100A6513

Страница 1: ...R FLATBLADE SCREWDRIVERWHENTURNINGADJUSTMENTPOTS SHARP OBJECTS CAN DAMAGE THE POT AND RESULT IN ELECTRICAL SHOCK AC DC CONNECTOR VERSION SENSORS ARE EQUIPPED WITH AN AC TYPE CONNECTOR THE USE OF DC POWER WITH AC TYPE CONNECTORS MAY NOT CONFORM WITH ESTABLISHED STANDARDS INTRODUCTION Thru beam sensors consist of a source and detector posi tioned on opposite sides of a detection zone The source emit...

Страница 2: ...e brightest The detector must be placed within the source beam pattern the area containing all the light rays emitted by the source The source must be placed within the detector field of view for the detection system to operate Only the light source rays that travel in a straight line to the receiver the diameter of the lens will be detected An object must fully block this beam in order to be dete...

Страница 3: ...IRING DIAGRAMS For wiring cable versions the color codes shown are the actual wire colors emanating from the sensor For connector ver sions the pin numbering and color codes shown are typical of several manufacturers however variations are possible In case of discrepancies rely on function indicated and pin location rather than pin number or color code AC DC Models AC Connection AC DC Models DC Co...

Страница 4: ...nsor will turn off immediately when a short or overload is detected Indicator LED will flash Protection Turn power OFF and back ON to reset IMPORTANT During installation correct power connections must be made first to ensure fail safe short circuit protection of the outputs Light Dark Operation Switch selectable on detector Temperature Range Operating and Storage Source 20 to 70 C 4 to 158 F Detec...

Отзывы: