Dynamic Braking Unit Installation Manual 

1. Preface 

Thank you for choosing CUTES’s breaking module.DBU30 braking unit helps dissipate regenerative energy from the three-phase 

induction motor when in applications that required sudden deceleration. With DBU30 Braking Unit, the regenerative energy will be 

dissipated in dedicated braking resistor. To prevent electrical fire or human injury, follow the instruction manual before wiring. The 

DBU30 braking unit is designed for use with the CUTES’s VFD models. The Braking Resistor is designed for use with  DBU30 

braking unit(Refer to this manual for more information).When ordering new copies of the manual, contact a CUTES representative 

or download on our documentation website

http://www.cutes.com.tw/

 

2. Specifications 

DBU Braking Unit Selection                                            Braking Resistor Selection

 

 

Operation Explanation

 

1. 

For safety consideration, 

install an overload relay 

between the braking unit and 

the braking resistor. In 

conjunction with the magnetic 

contactor (MC) prior to the 

drive, it can perform complete 

protection against 

abnormality. 

2. 

The purpose of installing 

the thermal overload relay is 

to protect the braking resistor 

from damage due to frequent braking, or due to braking unit keeping operating resulted from unusual high input voltage. Under 

such circumstance, just turn off the power to prevent damaging the braking resistor.

   

3. 

Please refer to the specification of the thermal overload relay. 

 

4. 

The alarm output terminals (RA, RC) of the braking unit will be activated when the temperature of the heat sink exceeds 

95°C. It means that the temperature of the installation environment may exceed 50°C or the braking %ED may exceed 10%ED. 