Confirm that the environmental conditions are consistent with the
following ranges:
•
Ambient Temperatures: Between -40° and +158°F.
•
Relative Humidity: Between 5% and 95% non-condensing.
•
Altitude: Less than 13,000 feet.
Before Installation:
System Configuration
Verification
CurrentGuard
™
and CurrentGuard
™
Plus Installation, Operation and Maintenance Manual
4
MODEL NOMINAL
L-N
L-L
CONFIGURATION
VOLTAGE VOLTAGE VOLTAGE
RANGE
RANGE
CG(P)xxx-120/240-2G
120/240
108-132
216-264
Split-Phase
3-wire+ground
CG(P)xxx-120/208-3GY
120/208
108-132
187-229
Three-Phase WYE
4-wire+ground
CG(P)xxx-220/380-3GY
220/380
198-242
342-418
Three-Phase WYE
4-wire+ground
CG(P)xxx-277/480-3GY
277/480
249-305
432-528
Three-Phase WYE
4-wire+ground
CG(P)xxx-347/600-3GY
347/600
312-382
540-660
Three-Phase WYE
4-wire+ground
Three-Phase
CG(P)xxx-120/240-3GHD 120/240
108-132
(
A
&
C PHASES
)
216-264
high-leg DELTA
187-229
(
B PHASES
)
4-wire+ground
CG(P)xxx-240NN-3DG
240
NA
216-264
Three-Phase DELTA
3-wire+ground
CG(P)xxx-380NN-3DG
380
NA
342-418
Three-Phase DELTA
3-wire+ground
CG(P)xxx-480NN-3DG
480
NA
432-528
Three-Phase DELTA
3-wire+ground
CG(P)xxx-600NN-3DG
600
NA
540-660
Three-Phase DELTA
3-wire+ground
(P) for CurrentGuard Plus
xxx denotes surge rating per mode (40, 60, 80, 100, 150 or 200)
Confirm that the voltage(s) and service configuration shown on the
CurrentGuard product label are consistent with the voltage and service
configuration of the facility. A model number is on the right side of
the CurrentGuard unit. Each model number corresponds to the con-
figurations printed in the table below:
Example of a SPD model number: CGP150-120/208-3GY
Environmental Condition
Verification