background image

7

SP-MODULE rev.04

SP-MODULE

Connecting the Sensor

To connect the sensor, refer to the wiring diagram.  Make sure the

power supply is suitable for the sensor (see technical specifications at

the end of this manual).

WARNING.  All wiring must be done by an authorized elec-

trician according  to all applicable codes, laws and regula-

tions.  Make sure that the power is off before doing any

wiring or opening the sensor to avoid electrical shocks and

equipment damage.

Pass all wiring through the bottom of the enclosure.  Do

not drill holes on the side or the top of the enclosure as this

may allow water to enter the enclosure.

To punch holes through the bottom, use a hammer and punch to carefully

punch the holes you need.

Never mount the sensor near water or rain pipes, as failure

of these pipes may cause strong water jets to reach the

sensor.

Do not under any circumstances change the setting of the

calibration potentiomenter inside the enclosure.  This will

decalibrate the pressure gauge.

Do not install ends of inlet (reference) and outlet (room)

tubes in walls, in insulation, in a humid environment or near

walls affected by drafts.

!

WARNING

!

WARNING

10

SP-MODULE

SP-MODULE rev.04

Span Adjustment (Complete the zero adjustment before setting span):

Span on full scale output adjustments should only be performed by using

an accurate pressure standard (electronic manometer, digital pressure

gage, etc.) with at least comparable accuracy to the SP-Module (668

Series) (<±1% full scale). With full scale pressure applied to the high

pressure port (reference port open to atmosphere) adjust span to achieve

20 mA output.

Example 1 : Unidirectional pressure range of 0 to 1"W.C. Apply

1.00"W.C., adjust span to 20 mA.

Notes: The input is reverse-voltage protected. The output is internally

protected against damage if shorted to ground. Recheck all

connections before applying power.

Содержание SP-MODULE

Страница 1: ...SP MODULE Static Pressure Module USER S MANUAL M 890 00102 rev 04 REV 00 ...

Страница 2: ...CAUTIONS 3 INSTALLATION 4 Description of the SP MODULE 4 Installing the Module on the Wall 4 Connecting the Sensor 7 Connecting the Output Wire 8 USING THE SENSOR 9 Description of the SP MODULE 9 TECHNICAL SPECIFICATIONS 10 WIRING DIAGRAMS 11 ...

Страница 3: ... F AND 104 F 0 C TO 40 C To avoid exposing the module to harmful gases or excessive humid ity it is preferable to install it in a corridor DO NOT SPRAY WATER ON THE MODULE FOR CUSTOMER USE Enter the serial number located on the side of the module below for future reference Model number Serial number SP MODULE ...

Страница 4: ...ive to vibrations In most cases preferred installa tion is with the baseplate mounted vertically and located on a relatively flat surface in a junction box or attached to a nearby beam Theaxismostsensitivetovibrationistheoneperpendicu lar tothe mounting base Avoid mounting with maximum vibration along this axis Pressure Fitting Both the positive high pressure port and the reference low pressure po...

Страница 5: ...w moments to write the complete serial number foundonthesideofthemoduleonpage1ofthismanual This will be useful for future reference A A A A B B Fig 1 Exploded view of the SP MODULE WARNING 3 75 in 95 mm 3 in 76 mm 4 8 in 122 mm 12 SP MODULE rev 04 WIRING DIAGRAMS COM OUT LOW HIGH EXC RECIVER LOAD MAIN CONTROLLER RECEIVERLOAD ...

Страница 6: ...if the attic is an adequate reference read the pressure difference between the attic and outside It should be close to zero Make a loop in both tubes room and reference to trap humidity Fig 3 11 SP MODULE rev 04 TECHNICAL SPECIFICATIONS Type SP MODULE Accuracy 1 of full scale RSS includes non linearity hysteresis and non repeatability Nominal operating voltage 14 28 VDC 13 24 VAC 50 60 Hz Operatin...

Страница 7: ...ach the sensor Do not under any circumstances change the setting of the calibration potentiomenter inside the enclosure This will decalibrate the pressure gauge Do not install ends of inlet reference and outlet room tubes in walls in insulation in a humid environment or near walls affected by drafts WARNING WARNING 10 SP MODULE SP MODULE rev 04 Span Adjustment Complete the zero adjustment before s...

Страница 8: ...output 4 20mA signal Output current Pressure Difference 20mA 4 0 4mA Fig 4 Output current vs pressure difference Calibration The SP Module 668 Series is factory calibrated and should require no field adjustment However both zero and span adjustments are provided Whenever possible any zero and or span offsets should be corrected by software adjustment in the user s control system Use the zero and s...

Страница 9: ...output 4 20mA signal Output current Pressure Difference 20mA 4 0 4mA Fig 4 Output current vs pressure difference Calibration The SP Module 668 Series is factory calibrated and should require no field adjustment However both zero and span adjustments are provided Whenever possible any zero and or span offsets should be corrected by software adjustment in the user s control system Use the zero and s...

Страница 10: ...ach the sensor Do not under any circumstances change the setting of the calibration potentiomenter inside the enclosure This will decalibrate the pressure gauge Do not install ends of inlet reference and outlet room tubes in walls in insulation in a humid environment or near walls affected by drafts WARNING WARNING 10 SP MODULE SP MODULE rev 04 Span Adjustment Complete the zero adjustment before s...

Страница 11: ...if the attic is an adequate reference read the pressure difference between the attic and outside It should be close to zero Make a loop in both tubes room and reference to trap humidity Fig 3 11 SP MODULE rev 04 TECHNICAL SPECIFICATIONS Type SP MODULE Accuracy 1 of full scale RSS includes non linearity hysteresis and non repeatability Nominal operating voltage 14 28 VDC 13 24 VAC 50 60 Hz Operatin...

Страница 12: ...w moments to write the complete serial number foundonthesideofthemoduleonpage1ofthismanual This will be useful for future reference A A A A B B Fig 1 Exploded view of the SP MODULE WARNING 3 75 in 95 mm 3 in 76 mm 4 8 in 122 mm 12 SP MODULE rev 04 WIRING DIAGRAMS COM OUT LOW HIGH EXC RECIVER LOAD MAIN CONTROLLER RECEIVERLOAD ...

Страница 13: ...SP MODULE Static Pressure Module USER S MANUAL M 890 00102 rev 04 REV 00 ...

Отзывы: