Installing Accessories
37
Cat. No. 01024514
Installing the Modem In the Remote
Open the remote monitor housing by removing the two screws and squeezing the sides of the monitor housing slightly.
Insert the modem board (P/N 01020747) into the socket on the back of the remote board (see Figure 48). Make sure that
all of the pins in all four connectors are aligned and make sure the modem is fully seated into all of the sockets. Snap the
two halves of the remote housing back together using light finger pressure and insert the two screws.
Figure 48.
Back of remote board.
Refer to the GBE Programming for Commercial Softeners and Filters, except HF xN Manual (P/N 01027295) for pro-
gramming information. This manual can be obtained from your local dealer, on C-Port (www.cport.culligan.com) under the
or on the Service Tech App.
Flow Meter
“Electrical Schematic” on page 24
for information regarding the flow meter connections.
Refer to the GBE Programming for Commercial Softeners and Filters, except HF xN Manual (P/N 01027295) for pro-
gramming information. This manual can be obtained from your local dealer, on C-Port (www.cport.culligan.com) under the
or on the Service Tech App.
Differential Pressure Switch
RJ11
PHONE
MODEM
BOARD
BASE BOARD
RF BOARD
AUXILARY BOARD
Figure 49.
Differential Pressure Switch Wiring
Wire from the common and normally
open contacts in the pressure switch
to Aux In.
Program Aux In for 10 minutes (600
seconds) then regen trigger
1/8”NPTx1/4” Tube Elbow
Differential Pressure Switch
Lo
Hi
Valve
Outlet
Valve
Inlet
Service Outlet
Inlet
1-1/2” Tee
1-1/2”x3/4” Reducing Bushing
3/4”x1/8” Reducing Bushing