66
Culligan® High Efficiency 1.5 Twin Water Softener
66
Cat. No. 01024821
Appendix B Flow Data
High Efficiency Twin 1.5 Water Softeners—Flow Rate Data (gpm)
Table 14.
High Efficiency 1.5 Twin flow rate data.
Model
Service
*Suggested
Progressive
Flow Trip
Point
Drain
Minimum Continuous Peak
Back-
wash
Brine
Draw
Slow
Rinse
Fast
Rinse
HE-060
2.1
25.1
31.5
18.8
5.5
0.93
0.73
5.5
HE-090
2.8
26.6
35.2
20.0
5.5
1.52
1.43
5.5
HE-120
2.8
23.3
31.8
17.5
5.5
1.48
1.19
5.5
HE-150
5
27.2
35.8
20.4
7.1
1.5
1.28
7.1
HE-210
11.5
28.0
37.4
21
11.5
1.9
1.6
11.5
*The Suggested Progressive Flow Trip Point is simply a suggested flow rate at which point an additional tank will be
brought on line if facility flow demand meets this rate. The Culligan Controller will not remove a tank brought on line by at-
taining the Trip Point unless the flow is <95% of the Trip Point amount for a 60-second period. In the event additional units
are not brought on line or off line when desired, simply adjust the programmed Trip Point. Refer to the system instruction
manual, Operation and Programming sections for more information about the Progressive Flow mode of operation.