TD040600-0I

C

 

 

Powering 

The EISB requires low-voltage power  (AC or DC) via a four-pin removable 
keyed connector.  Power conductors can be stranded (16–18 AWG) or solid 
(16–22 AWG).  Consult the Specifications section for power requirements.  
The various power options are explained below. 

NOTE:

  

This device is intended for use with Class 2 circuits.

 

DC Powered 

The EISB accepts a voltage range of 10–36 VDC and draws a current value 
commensurate with 20-watt power consumption.  Power conductors should be 
sized accordingly.  Ground is directly connected to zero volts and the 
equipment chassis is isolated from zero volts.  The input connections are 
reverse-polarity protected. 

Figure 6 — DC Powered 

Redundant DC Powered 

Redundant diode-isolated DC power inputs are provided so the EISB can 
operate despite the loss of primary power.  Either source must be capable of 
providing 20 watts of power. 

Figure 7 — Redundant DC Powered 

 

Содержание EISB Series

Страница 1: ...ch port negotiates flow control supporting the PAUSE function for full duplex segments and the backpressure scheme for half duplex segments All units offer non blocking wire speed operation with a max...

Страница 2: ...al Compliance ANSI IEEE 802 3 Data Rate 10 Mbps and 100 Mbps Signaling 10BASE T 100BASE TX 100BASE FX LED Indicators Power red green Ports green yellow Managed Switch LEDs Status red green Console gre...

Страница 3: ...sed Figure 2 RJ 45 Connector Console Port EIA 232 Pin Assignments PIN Signal Function 2 RXD Receive Data 3 TXD Transmit Data 5 GND Ground All other pins are unused Figure 3 DB9 Pins Figure 4 Null Mode...

Страница 4: ...reinforced DIN rail clip is pre attached to the back of the EISB enclosure with two 4 40 pan head screws If the clip is removed the EISB can be panel mounted by extending the top and bottom brackets...

Страница 5: ...er media regardless of data rate Although 10BASE T links can use Category 3 4 or 5 cable 100BASE TX segments must use Category 5 or higher A popular choice for improved distance is multimode fiber whi...

Страница 6: ...EISB accepts a voltage range of 10 36 VDC and draws a current value commensurate with 20 watt power consumption Power conductors should be sized accordingly Ground is directly connected to zero volts...

Страница 7: ...MR is for use with 120 VAC The AI XFMR E is for use with 230 VAC Figure 8 AC Powered Figure 9 AC Powered with Grounded Secondary AC Powered with Battery Backup The EISB can also operate in the AC mode...

Страница 8: ...ssociated with those ports nearest the front of the case LEDs further from the line correspond to ports closer to the rear of the case As an example of port arrangement Figure 11 identifies a few of t...

Страница 9: ...disaster misuse or incorrect installation User modification may void the warranty if the product is damaged by the modification in which case this warranty does not cover repair or replacement This w...

Страница 10: ...temporary Controls Ltd Sovereign Court Two UWSP Sir William Lyons Road Coventry CV4 7EZ UNITED KINGDOM Type of Equipment Industrial Ethernet switching hubs 8 port Models 16 port Models 24 port Models...

Отзывы: