CTC GS 6-8

 

More settings and tips in the installation and service manual

Fine adjustment Increase/decrease heat

If the outdoor 

temperature is lower 

than 0°C. 

Change inclination

Coarse adjustment Increase/decrease heat

Select: 

Heating circuit

+

+

+

If the outdoor 

temperature is higher 

than 0°C. 

Change adjustment

Heating circuit

Max primary flow ºC 

60

Min primary flow ºC 

Off

Heating, mode 

Auto

Heating, mode, ext

Heating off, out ºC 

18

Heating off, time 

120

Inclination ºC 

50

Adjustment ºC 

0

Night reduction disable ºC 

-14

Room temp reduced ºC 

-2

  or

Primary flow reduced ºC 

-3

Alarm room temp ºC 

5

Smart low price ºC 

1

Smart over capacity ºC 

2

Max time heating 

20

Charge pump % 

60

Drying period mode 

Off

Drying period temp ºC 

25

Push OK to confirm 

changes

+

Set heating

1

2

Night reduction

Holiday

Heating circuit 2 (50)

Heating System 1

Room temp.

Measured temp 

Room sensor

Desired  

Setpoint

1

2

Night 
reduction

-Set a higher 
or lower 
temperature at 
certain times of 
day.

Holiday

-Set higher or 
lower temperatures 
on certain days.

Fine adjustment with 
no room sensor. To 
allow the temperature 
to be changed even 
more, use the coarse 
adjustment on the 
right.

Change hot tap water temperature

For detailed information on other hot 

water settings, please refer to the 

Installation and Maintenance instructions.

Control normal mode for hot water 

production.

Economic – Small DHW requirement. 

Normal – Normal DHW requirement. 

Comfort – Large DHW requirement.

Weekly program

- Set weekly interval 
for extra hot water

Set hot water

The product will start to 

produce additional hot 

water.

Extra

 

hot water

 

0.0

 hours

On
Temperature
Normal

Weekly program

DHW

Installer

“Installer” is used by the installer to configure the settings and servicing for 
your heating system. 

Allow additional heat and immersion heater for safe comfort 
at all times

To ensure hot water comfort in all operating conditions, it may be 
necessary to allow additional heat. If there is no heat pump or other 
heat source installed, these settings need to be changed so that 
the product can function as an electric boiler.

Select: Hot 

water tank

+

+

Change:  

Add heat DHW – Yes

+

1

2

2

Rumstemperatur Varmvatten 

1

2

2

Rumstemperatur Varmvatten 

1

2

2

Содержание GS 6-8

Страница 1: ... the pre pressure in the expansion tank 7 Regularly clean the dirt filter close off incoming tap water remove and clean the filter solenoid filter ball valve close off the flow to the heat pump remove and clean the filter 8 Set the correct heating curve for a comfortable room temperature check that the thermostat valves on the element or floor heating are set up correctly These may need to be open...

Страница 2: ...e house Clean safe hot water The water in the tank as in the heat pump and radiators rises and is layered so that the hottest water surrounds the DHW heat exchanger where the tap water flows through quickly draws energy and flows out to the tap or shower This provides fresh hot water and minimises the risk of legionella bacteria Cooling module The energy in the bore hole bedrock or ground is drawn...

Страница 3: ...n CTC GS 6 8 Options with CTC GS 6 8 In addition to the basic installation accessories are required such as Extra sensor mixing valve group 2 expansion card etc Volume tank CTC VT 80 may be required for some houses see installation manual for more information 1 ...

Страница 4: ...e value Press to decrease value Arrow OK Press up arrow to increase value Press OK to save settings Press down arrow to decrease value Home screen Larm E055 Fel fasföljd Återställ larm Larm Fel fasföljd kompressor Återställ larm Green LED status OK Red LED alarm The serial number 12 digits can be found behind the display This number needs to be given to the installation engineer and CTC support in...

Страница 5: ... lower temperatures on certain days Fine adjustment with no room sensor To allow the temperature to be changed even more use the coarse adjustment on the right Change hot tap water temperature For detailed information on other hot water settings please refer to the Installation and Maintenance instructions Control normal mode for hot water production Economic Small DHW requirement Normal Normal DH...

Страница 6: ...tting inclination 50 High temperature system older houses small radiators poorly insulated inclination 60 Example in image 1 Inclination 50 Adjustment 0 2 Inclination 40 Adjustment 0 3 Inclination 50 Adjustment 5 Find the right heating curve The heating curve for the house is determined by two main factors inclination and adjustment These can be changed to fit the house s energy needs for heating ...

Страница 7: ...the thermostat valves on the house s element are open in most rooms only adjust downwards in bedrooms for example Use the DHW chart for extra DHW to avoid high temperature operation when it is not needed Install a room sensor this provides more even heat and compensates for natural solar radiation or other natural heat sources Clean any dirt filters regularly a deterioration in water flow can incr...

Страница 8: ...y valve function test Waste pipe connected to floor drain Electrical installation Omnipolar switch If the heat pump is installed heat pump activated and started Electric power kW and fuse adapted to the property in heating mode in hot water mode and backup mode Correct tight wiring Requisite sensors for selected system Outdoor sensor Room sensor optional Current sensor Accessories Information for ...

Отзывы: