Important!

•  Read carefully before use, keep for future reference.

•  Translation of the original instructions.

Installation and Maintenance Manual

CTC EcoPart Pro/Basic

Model i425-i435 / 425-435

Содержание EcoPart 425

Страница 1: ...solutions worldwide 162 505 99 1 2020 09 17 Important Read carefully before use keep for future reference Translation of the original instructions Installation and Maintenance Manual CTC EcoPart Pro B...

Страница 2: ...screws 4 Pull the cooling module by first lifting the front edge slightly with the carrying handles 5 Lift the cooling module using the carrying handles and shoulder straps 6 Lift the cooling module...

Страница 3: ...162 505 99 1 2020 09 17 Installation and Maintenance Manual CTC EcoPart Pro Basic Model i425 i435 425 435...

Страница 4: ...Groundwater heating________________________________________26 5 Connecting the control system _________________________ 27 5 1 CTC EcoPart i425 i435 Pro_______________________________27 5 2 CTC EcoPar...

Страница 5: ...o the relevant manuals for these products The CTC EcoPart i425 i435 is a heat pump which takes heat from rock ground or lake and supplies it to the existing heating circuit in the house The heat pump...

Страница 6: ...brations Ensure that pipes used between the heat pump and the heating circuit are of adequate dimensions Register the product for warranty and insurance via the website https ctc se kundservice garant...

Страница 7: ...quired Open radiator valves depending on type of system and other relevant valves Tightness test Bleed the system Check proper operation of the requisite safety valves Requisite waste pipes connected...

Страница 8: ...larly qualified persons in order to avoid a hazard Safety valve check Safety valve for boiler system to be checked regularly The product must not be started if it is not filled with water instructions...

Страница 9: ...W 8 kW 17 kW 17 kW 17 kW 17 kW 1 Introduction This heat pump is available in many different versions depending on how you intend to control it The CTC EcoPart i425 i435 Pro has an integrated CTC EcoLo...

Страница 10: ...Pa 5 9 6 kPa 5 5 3 5 kPa l s 0 81 0 39 0 81 0 56 LEP Low Energy Pump Electrical data Name Type Operating system Rated power Rated current IP class Max operating current Compressors Max operating curre...

Страница 11: ...mpressor Name Type Operating system Rated power Rated current Protection class IP Max operating current Compressors Max operating current Compressor Max starting current Operational data for heat pump...

Страница 12: ...24 0 34 0 34 8 6 4 3 8 6 8 6 l s 0 68 0 48 0 68 0 68 LEP Low Energy Pump Electrical data Name Type Operating system Rated power Rated current IP class Max operating current Compressors Max operating c...

Страница 13: ...r sensor in 11 Drain valve warm side Water 12 Conduit for communication concealed 13 CTC Basic Display only CTC EcoPart standard version 14 High pressure sensor 15 Drying filter 16 Low energy brine pu...

Страница 14: ...163 243 0 163 243 80 80 164 164 0 88 138 188 428 Erforlig resh jd 1855mm Ko Skala Ritad Material Datum Sign Distr till Antal Ytj mnhet RA Om ej annat angives 1 20 DP 2014 09 16 Reservdel 2 4 Dimension...

Страница 15: ...ature brine 15 Temperature water out 16 Temperature water in 17 Control expansion valve 2 5 Refrigerant system The schematic diagram shows the refrigerant system for each integrated heat pump module 2...

Страница 16: ...sion vessel in an open or closed system Do not forget to flush the heating circuit clean before connection Apply all the installation settings based on the description in the chapter on First start Th...

Страница 17: ...4 x Non return valve 1 4 x Dirt filter 1 4 x Rubber grommet D 60 4 x Edge moulding 186 mm 2 x Edge moulding 700 mm CTC EcoLogic M L CTC EcoPart 425 435 with two CTC Basic Display units 1 x Safety valv...

Страница 18: ...fasten the protective edging provided around the edge of the opening in the insulation plate Adjust the length of the protective edging to suit the opening as required 2 Pass the hoses through the ope...

Страница 19: ...cting pipe depends on the installation Route the pipes so that no other highest point is present where air can collect and obstruct circulation If however this cannot be done provide this highest poin...

Страница 20: ...is supplied with two LEPs Low Energy Pump which are low energy charge pumps installed at the factory 3 4 1 Yonos Para pump curve 3 4 2 UPMGEO pump curve Circulation pump 8 kW Yonos Para PWM 7 0 Prod...

Страница 21: ...re important that no water based lubricants and similar are used during installation It is also important that all the components are insulated against condensation to prevent the build up of ice i We...

Страница 22: ...9 when filling and bleeding the brine system i The mixing vessel and pump must be of a good size Valves To facilitate servicing of the cooling unit shut off valves must be fitted to both the incoming...

Страница 23: ...lation check on brine system After a few days you must check the fluid level in the vessel Fill if necessary and close the valves 98c and 98d when filling Expansion vessel level vessel The vessel shou...

Страница 24: ...Checking brine difference When the heat pump is running regularly check that the temperature difference between incoming and outgoing brine temperatures is not too large If there is a large differenc...

Страница 25: ...2 4 6 8 10 12 m H 0 20 40 60 80 100 120 kPa p 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 Q l s 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 5 5 Q m h 0 40 80 120 160 W P1 Heat pump module 8 kW 10 kW 12 kW 14...

Страница 26: ...fuse should also be used Cable approved for 230 V AC must be used for connecting this output irrespective of the load that is connected For connection information see the wiring diagram 4 2 Groundwate...

Страница 27: ...i435 Pro has an integrated CTC EcoLogic L control unit with touchscreen The CTC EcoPart 425 435 has two CTC Basic Display units connected to each cooling module The left hand display is connected to t...

Страница 28: ...module A2 5 2 CTC EcoPart 425 435 The CTC EcoPart 425 435 has two CTC Basic Display units mounted behind the front panel The displays are used to address the cooling modules when connecting more than...

Страница 29: ...in the communication cable must be connected to earth see below 5 3 1 Terminated position The last heat pump connected in series must be terminated This is achieved with a DIP switch located on the ci...

Страница 30: ...ontrol terminal block and PE on the mains terminal block must also be removed and replaced by the shielding which is then connected up to the next heat pump control terminal block position Sc This mus...

Страница 31: ...n Positions of the DIP switches in the example Last cooling module in the series connection A10 Cooling modules A1 and A2 Cooling modules A3 A9 Cooling module A10 Display setup Brown White Green Brown...

Страница 32: ...EcoZenith i555 Pro as well as the CTC EcoPart 600M to be numbered as Heat Pump 2 VP2 3 Wait for about 2 minutes 4 Go to Installer Service Set Address Select Current address press OK and press the dow...

Страница 33: ...8 Go to Service Set Address Select Current address press OK and press the down arrow until the current heat pump appears VP1 Press OK Select New address press OK and press the up arrow until the curr...

Страница 34: ...mbered and energised they should be displayed when you press the heat pump symbol in the menu Operation data If any heat pump does not appear in the menu communication with the heat pump fails It may...

Страница 35: ...w darkens In this example we have assumed that the heat pump is called A1 which is the factory default If the heat pump has already been renumbered then select this number instead 5 4 4 Numbering CTC...

Страница 36: ...ress OK After pressing OK A1 disappears and the Select Rename Heat Pump row darkens The heat pump is now numbered A3 In this example we have assumed that the heat pump is called A1 which is the factor...

Страница 37: ...communication with the heat pump fails It may be because it has not been numbered as described above If you do not know the name of the heat pump you can reset the numbering by using the Select Renam...

Страница 38: ...38 CTC EcoPart i425 i435 Pro 5 5 Wiring diagram for CTC i425 i435 Pro 400V 3N...

Страница 39: ...39 CTC EcoPart i425 i435 Pro...

Страница 40: ...40 CTC EcoPart i425 i435 Pro 5 6 Electrical diagram cooling module 400V 3N CTC EcoPart 406 417...

Страница 41: ...41 CTC EcoPart i425 i435 Pro...

Страница 42: ...42 CTC EcoPart i425 i435 Pro 5 7 Electrical diagram CTC EcoPart i425 i430 Pro 230V 1N...

Страница 43: ...43 CTC EcoPart i425 i435 Pro...

Страница 44: ...44 CTC EcoPart i425 i435 Pro 5 8 Power supply and communication 230V 1N CTC EcoPart 425 430...

Страница 45: ...45 CTC EcoPart i425 i435 Pro 5 9 Power supply and communication 400V 3N CTC EcoPart 425 435...

Страница 46: ...46 CTC EcoPart i425 i435 Pro 5 10 Electrical diagram cooling module 230V 1N...

Страница 47: ...6 18 120 7 13 115 8 26 110 9 59 105 11 17 100 13 06 95 15 33 90 18 1 85 21 4 80 25 4 75 30 3 70 36 3 65 43 6 60 52 8 55 64 1 50 78 3 45 96 1 40 119 35 147 30 184 25 232 20 293 15 373 10 479 5 619 150...

Страница 48: ...7 115 1167 110 1330 105 1522 100 1746 95 2010 90 2320 85 2690 80 3130 75 3650 70 4280 65 5045 60 5960 55 7080 50 8450 45 10130 40 12200 35 14770 30 18000 25 22000 20 27100 15 33540 10 41800 5 52400 0...

Страница 49: ...NTC 015 B23 Brine in Type 1 NTC 22 B24 Brine out Type 1 NTC 22 B27 HP in Type 2 NTC 22 B28 HP out Type 2 NTC 22 B43 Sensor external DHW tank NTC 22 B50 Sensor pool NTC 22 B100 High pressure sensor B10...

Страница 50: ...installer show you where the power switches controls and fuses are so that you know how the system works and how it should be maintained Bleed the radiators depending on type of system after around th...

Страница 51: ...a fault occurs you should always contact the installer who installed your unit If the installer believes the malfunction is due to a materials or design fault then they will contact Enertech AB to che...

Страница 52: ......

Страница 53: ......

Страница 54: ......

Страница 55: ......

Страница 56: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 012 162 505 99 1 2020 09 17...