The configuration screen displays the overall system settings that can be adjusted
to the desired CIP wash parameters by allowed users .
WASH SETTINGS
Wash settings include Time, Temperature (Temp), Conductivity (Cond), Flow, and
Chemical (Chem) Setpoints (SP) for each wash phase — from Pre-rinse to Sanitizer .
The Compact CIP will not advance to the next step in the wash cycle until the
system is either above or below the setpoint .
Pre-rinse
— waits until the system is at or above Flow SP and below Cond SP .
Caustic
— waits until the system is at or above Cond SP, Temp SP, and Flow SP .
Rinse
— waits until the system is at or above Flow SP and below Cond SP .
Acid
— waits until the system is at or above Temp SP, Cond SP, and Flow SP .
Drain
— waits until the system is tank is below low limit SP .
Final Rinse
— waits until the system is at or above Flow SP and below Cond SP .
Sanitizer
— waits until the system is at or above Flow SP and below Cond SP .
For example, in the screenshot shown above, the Pre-rinse phase will not advance
to the Caustic phase until the Flow SP is at or above 20 .0 and the Cond SP is
below 2 .0 . The Temp SP has a value of N/A which indicates that there is neither a
minimum nor maximum requirement for the Pre-rinse Temperature (Temp SP) and
therefore will not delay advancement to the next phase .