Loop water out sensor
Sustained shut down on first fault
•
Common loop water return sensor
With multiple chillers if the #1 sensor fails the system will use the next available water return
sensor and the unit will continue to run.
If all the return sensors fail, the system will use the common loop water supply sensor to monitor
stage set points.
•
Common loop water supply sensor
The system will continue to operate
•
Sea water out sensor
The system will continue to operate
•
Sea water in sensor
The system will continue to operate and will use the next available sea water in senor, if
available.
•
Immersion heater loop water sensor
Will use next available immersion heater loop water sensor and system continue to run.
If extra sensor is not available, then all heaters will be sustained shutdown.
System Faults for Sensors (cont’d.)