INSTALLATION AND OPERATION MANUAL, ELECTRIC BOILERS, 

CE24, CE36, CE42, CE48, CE324, CE336, CE342, CE348

3.0  OPERATING INSTRUCTIONS

For CSD-1 equipped boilers, see section 4.0 CSD-1 Optional Feature for proper operating
instructions.

BOILER CONTROLS (Inside Cabinet)

Main Power Switch 

ON fills the boiler tank and turns the boiler heaters on.  You should
allow 20 minutes to fill the tank and generate steam.

OFF shuts off the boiler heaters and opens the Automatic
Blowdown Valve, emptying the boiler tank and releasing water and
steam to the drain.  This should be done daily to remove sediment,
lime, or scale.

Pilot Light

-

Indicates main power is ON.

Boiler Pressure Gauge -

Should read 9 - 11 psig during operation; 0 psig during shutdown.

Water Level Sight Glass-

Observe level of water and water quality in the boiler.  Murkiness in
the water indicates inadequate water quality; the owner must supply
proper water to the boiler (see page 4).

Water Level Control -

While boiler is ON, briefly open the water level control valve once a
day to remove any sediment that might accumulate.  (See page 12
for detailed instructions.)

Safety Valve  -

This valve will release (pop off) if the boiler has too much pressure. 
Once a week, this valve should be tripped during operation to make
sure it functions properly.

OPERATION OF THE BOILER

Turn on water and power supply.

Open cabinet door and turn main power switch ON.  Pilot light ignites and water begins to fill
boiler - observe water gauge sight glass to verify that proper water level is reached.

Once the proper water level is reached, the heaters begin to heat the water.  Heaters require
about 15 minutes to begin steam generation.  The boiler pressure gauge in the cabinet should
indicate steam pressure in a range of 9 to 11 psig.

Part No. 10044R5

8

2017-12-27

Содержание CE-24

Страница 1: ...ing and maintenance instructions thoroughly before installing or servicing this equipment IMPORTANT FOR FUTURE REFERENCE Please complete this information and retain this manual for the life of the equ...

Страница 2: ...void possible injury or death WARNING Improper installation operation adjustment alteration service or maintenance can cause property damage injury or death Read the installation operating and mainten...

Страница 3: ...42 CE48 CE324 CE336 CE342 CE348 TABLE OF CONTENTS DESCRIPTION PAGE 1 0 Service Connections 4 2 0 Installation Instructions 5 3 0 Operating Instructions 8 4 0 CSD 1 Optional Feature 10 5 0 Periodic Mai...

Страница 4: ...INSTALLATION AND OPERATION MANUAL ELECTRIC BOILERS CE24 CE36 CE42 CE48 CE324 CE336 CE342 CE348 2 0 SERVICE CONNECTIONS Part No 10044R5 4 2017 12 27...

Страница 5: ...k that there are sufficient clearances to service the controls door swing etc Also adequate clearance must be left for making the required supply and drain connections Allow enough space between any o...

Страница 6: ...installation position 6 Place carpenter s level on top appliance and re level side to side and front to back 7 Bolt and anchor appliance securely to the floor 8 Seal bolts and flanged feet with silas...

Страница 7: ...he rear of the boiler cabinet requires 3 8 tubing and water pressure of 25 50 psig A manual shut off valve must be provided convenient to the boiler this valve should be open when the boiler is in ope...

Страница 8: ...y in the boiler Murkiness in the water indicates inadequate water quality the owner must supply proper water to the boiler see page 4 Water Level Control While boiler is ON briefly open the water leve...

Страница 9: ...E336 CE342 CE348 3 0 OPERATING INSTRUCTIONS Continued SHUT DOWN Turn the Main Power Switch OFF Open manual drain valve If unit is supplied with Automatic Blowdown Valve it will open draining the boile...

Страница 10: ...ched the proper level the level control will stop the flow of water to the boiler As water is consumed in the production of steam the level control will supply additional water to the boiler Firing Cy...

Страница 11: ...A high pressure safety switch is installed on the boiler Should the pressure exceed the limit of this device the boiler will be shut down and put into a state of lockout The PRESSURE pilot light red...

Страница 12: ...t the accumulation of sediment does not interfere with the movement of the float in the control Control must be flushed at least once a day CAUTION Protect yourself When flushing control hot water and...

Страница 13: ...extra caution when blowing down water level control or tripping safety valve as extreme hot water and live steam are present DESCALING BOILER It is recommended that the boiler be checked every 90 to...

Страница 14: ...ning DO NOT TURN ON STEAM to attached appliances or to upper compartment 7 Open both the blowdown and low water level control valves for complete drainage After boiler drains close both valves 8 Turn...

Страница 15: ...ressure too low Automatic blowdown valve does not drain 1 Defective blowdown valve 2 Heat exchanger build up of scalant clogging drain lines and valve Boiler achieves pressure slower than normal 1 Hea...

Отзывы: