CROWN VERITY SW-24 Скачать руководство пользователя страница 8

SW Series Manual

8

9

1.0

 Safety

 

 Standards, Certifications and Government Regulations

Standards, Certifications and Government Regulations

Installation of this infrared heater must comply with all applicable local, state and national specifications, 
regulations and building codes. Contact the local building inspector and/or fire marshal for guidance. 

The heater must be electrically grounded in accordance with the following codes:

 

United States:

  Refer to National Electrical Code

®

, ANSI/NFPA 70 (latest edition).    

 

 

  Wiring must conform to the latest edition of National Electrical  

 

 

 

  Code

®

, local ordinances, and any special diagrams from the manufacturer.

 

Canada:

   Refer to Canadian Electrical Code CSA C22.1 Part 1 (latest edition).

Crown Verity units comply or are certified by one or more of the following organizations or 

standards:

 

•  CSA 22.2 #46 - M1988

 

•  UL 2021, 1997

Содержание SW-24

Страница 1: ...nd 3 Lamp Units WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury or death Read and understand the installation operating and maintenance inst...

Страница 2: ...cations 4 Clearance to Combustibles 5 Safety Signs and Labels 7 Standards Certifications and Government Regulations 8 2 0 Installation 9 Design 10 Heater Mounting 11 Lamp Installation 13 Outdoor Appli...

Страница 3: ...ars and vehicle maintenance shops For maximum safety the building must be evaluated for potential hazards before installing the heater system A critical safety factor to consider before installation i...

Страница 4: ...0 1ph 10 42 3 480 1 or 3ph 15 625 7 500 25 590 SW 46 1 480 1ph 7 60 3 650 12 454 575 1ph 6 60 3 800 12 978 2 480 1ph 15 21 7 300 24 909 575 1ph 13 22 7 600 25 955 3 480 1 or 3ph 22 81 10 950 37 636 57...

Страница 5: ...talling the heater system Examples include but are not limited to Gas and electrical lines Combustible and explosive materials Chemical storage areas Areas of high chemical fume concentrations Provisi...

Страница 6: ...950 11 400 0 24 24 24 6 96 45 96 24 24 10 96 A minimum clearance of 36 inches must be maintained from behind another heater NOTE Ensure that building materials with a low heat tolerance i e awnings fa...

Страница 7: ...ent to heater s controller SAMPLE DETROIT RADIANT PRODUCTS COMPANY 21400 HOOVER ROAD WARREN MI DETROIT RADIANT INFRARED RADIANT ELECTRIC HEATER FOR INDOOR COMMERCIAL INDUSTRIAL USE FOR PROTECTED AND U...

Страница 8: ...re marshal for guidance The heater must be electrically grounded in accordance with the following codes United States Refer to National Electrical Code ANSI NFPA 70 latest edition Wiring must conform...

Страница 9: ...llation manual along with national state provincial and local codes address these issues It is critical that you read understand and follow all guidelines and instructions Always inspect and evaluate...

Страница 10: ...re mounted too low or too high they may result in discomfort or lack of heat Chart 2 2 Indoor Spot Heating Application Chart Heater installation shall comply with all IOPM NEC ANSI NFPA 70 CEC and loc...

Страница 11: ...y or a factory representative for additional information on signage compliance The heater can be suspended with chains or rigid threaded rod Local codes or conditions that would cause the unit to move...

Страница 12: ...On each side place 1 1 4 x 1 2 bolt through slot in the mounting bracket and the hole in the top wire raceway Place 1 1 4 lock nut on each bolt and tighten 4 Tighten lock nuts from Step 1 5 Hook heat...

Страница 13: ...vice access panels and open lamp retainers 2 Position heating elements in U slots at the ends of the reflector When utilizing the ruby lamps the lamp adapter plates EL 006 must first be removed 3 Clos...

Страница 14: ...s should always be through one of the knockouts in the top wire raceway Wire connections must also be made outside the of the top wire raceway Consult the factory or a qualified electrician for detail...

Страница 15: ...ce Figure 2 12 Three Phase Service Figure 2 9 SW Wiring Diagram Units with 2 Lamps Figure 2 10 SW Wiring Diagram Units with 3 Lamps LAMP NO 1 L1 L2 LAMP NO 1 L1 L2 LAMP NO 2 LAMP NO 1 L1 L2 LAMP NO 2...

Страница 16: ...tibles 4 Check electrical wires and connections for wear or any kind of damage It is recommended that the following become a standard yearly procedure to obtain maximum operating efficiency and troubl...

Страница 17: ...nual Find the source of the electrical problem between panel and heater No No Yes Yes Is there a sufficient amount of heat Is the supply voltage correct for the model type on the rating label Is the h...

Страница 18: ...ts For complete information on SW Series replacement parts visit www crownverity com For discontinued models consult the factory 012 013 014 106 206 306 152 153 154 252 253 254 352 353 354 002 003 004...

Страница 19: ...h Star Washer Self Threading Fine threads 3 8 EL 088 Lamp 3800W 575V Ruby Single Lamp Model Parts List EL 027 1 4 20 x 1 2 inch bolt for bracket EL 106 Service Access Panel Single Lamp EL 028 1 4 20 N...

Страница 20: ...sis of a defective condition in the heater or for the installation of replacement parts The warranties provided herein will not apply if the input of the heater exceeds the rated input at time of manu...

Отзывы: