TABLE 14.0 - DIAGNOSTIC CONDITIONS

Condition

Possible Cause

Burner will not fire

See Flow Chart 1, page 46

Burner will not shut down

See Flow Chart 2, page 47

Temperature display exceeds 

high limit setting

Under normal operation, boiler temperature will continue to rise after the control shuts off 

the burner.  This condition, known as “thermal stacking”, results from hot boiler surfaces 

continuing to release heat into the boiler water.

No or insufficient domestic hot 

water

For boilers equipped with a tankless coil, make sure the low limit setting on the control is 

set properly. 

NOTE:

 If the low limit setting is dialed fully counterclockwise, it will shut 

off the low temperature maintenance feature and will function as a cold start control.  If 

installed with an indirect water heater, check that the Zone/Indirect Switch is set in the 

Indirect (I) position. Verify that the end switch in the relay box controlling the indirect water 

heater is connected to the ZC-ZR terminals. This will ensure that the domestic water calls 

are prioritized.

Low water light (Red LED) is on 

or blinking

WARNING

: A low water condition is a serious and potentially 

dangerous condition. Do not attempt to add water to a hot boiler. 

Allow the boiler to fully cool before adding water.

When the LOW WATER light is on, this indicates that the control is not detecting water 

in the boiler. When the LOW WATER light is blinking, this indicates that the control has 

been programmed to provide low water lock-out protection and is currently locked out (see 

Manual Reset Low Water Cut-Off). Pressing the TEST/SETTINGS button after the low 

water condition is resolved will reset the lock-out condition.
1. If the light is on and the heating system is filled with water, pull the sensor out of the well 

and inspect it. Make sure that the metal clip is protruding enough to come in contact with 

the inside of the well tube. Check that the well does not have excessive build-up of heat 

transfer grease that may interfere with the clip contacting the well.
2. Remove well and examine for excessive residue build-up. Clean and re-install.

House will not get or stay warm

1. Check for air-bound radiators.

2. Check thermostat settings including heat anticipator settings (common on non-digital    

thermostats).

3. Check the Economy setting. The Economy feature, much like outdoor reset controls, 

lowers average boiler temperature and can slow or, in some cases, prevent the house from 

coming up to temperature. Move to a lower setting (see “Setting the Economy Feature”).

Circulator contacts

C1 and C2 not energized on call 

for heat

Check to see that boiler water is at or above 125°F. On a call for heat, the control will 

not permit the circulator to operate if the boiler water temperature is below 125°F (see 

“Circulator Hold Off”).

All LED lights and temp display 

are blinking

If the LED lights and the temp display are blinking alternately, this indicates the control has 

sensed a boiler temperature of 250°F. When this occurs, the control pulses the burner relay 

and then shuts down and locks-out the burner. The system should be analyzed to determine 

the cause of the overheating condition. Check that the sensor is inserted all the way into 

the well so it can accurately sense the temperature of the boiler water. Check the load on 

the burner contacts: If the load exceeds the 7.4 Amp rating, the contacts may have welded. 

Correct the overloading condition and replace the control before reenergizing the system. 

If the load on the contacts is below the rating, check system wiring and operation as well 

as the control’s high limit setting. If the cause of the overheating is found and the system is 

deemed safe, the control can be reset by removing power from the control and then repow

-

ering while simultaneously pressing the Test/Settings button on the top of the control. If the 

cause of the overheating condition is not determined, the control should be replaced.

Содержание FWZ Series

Страница 1: ...www crownboiler com WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury or loss of life For assistance or additional information consult a qual...

Страница 2: ......

Страница 3: ...the manufacturing process as well as condensation during storage Surface rust is normal and does not affect the performance or longevity of a boiler All boilers must be installed in accordance with N...

Страница 4: ...start of the heating season The inside of the combustionchamber theventsystemandboilerfluewaysshouldbecleanedifsootorscalehasaccumulated When cleaning this boiler take precaution to avoid damage to bu...

Страница 5: ...service Improper installation adjustment alteration service or maintenance may cause serious property damage personal injury or death DO NOT DISCONNECT PIPE FITTINGS on the boiler or in the heating s...

Страница 6: ...ons for adequate combustion and ventilation air This boiler is supplied with controls which may cause the boiler to shut down and not re start without service If damage due to frozen pipes is a possib...

Страница 7: ...1 22 1 4 24 6 11 08 20 29 545 FWZ100 22 1 4 24 6 11 08 20 29 545 FWZ130 28 1 4 30 6 14 46 27 29 658 FWZ160 34 1 4 36 7 17 84 34 29 771 Maximum working pressure Water 50psi TABLE 2 1 RATING DATA FWZ Se...

Страница 8: ...W FRONT VIEW REAR VIEW NOTE THIS DIMENSION INCREASES AND IS CONTROLLED BY SMOKEPIPE FLAME OBSERVATION GAUGE PORT TEMP PRESSURE BURNER RELIEF LINE FLOOR BURNER BECKETT AFG VALVE SWING DOOR 1 1 2 FPT SU...

Страница 9: ...ystems including a Crown Mega Stor indirect water heater size the boiler to have either the Heating Capacity re quired for the Mega Stor or the I B R Net Rating required for the heating system whichev...

Страница 10: ...d other piping trim as described in the Venting and Piping sections of this manual 5 Different baffle arrangements are used based on the boiler size and choice of burner In some cases these baf fles a...

Страница 11: ...Yes3 FWZ130 FWZ0041 Beckett 41130B No No No Yes No FWZ130 FWZ0041 Riello 41130R No No No Yes No FWZ130 FWZ0041 Carlin 41130C Yes3 Yes No Yes Yes3 FWZ160 FWZ0051 Beckett 41160B No No No Yes No FWZ160...

Страница 12: ...10 FIGURE 4 2 BAFFLE AND BLANKET INSTALLATION...

Страница 13: ...Also see Figure 5 0 Front 24 from front Jacket surface Left Side 6 Right Side 6 Rear 12 Top 6 Single Wall Chimney Connector to combustible construction 18 A 24 service clearance is recommended above t...

Страница 14: ...ied to areas such as joints around window and door frames between sole plates and floors between wall ceiling joints between wall panels at penetrations for plumbing electrical and gas lines and at ot...

Страница 15: ...ling and the bottom edge of the lower opening must be within 12 of the floor Figure 6 0 Each opening must have a free area of 1 square inch per 1000 BTU hr input of all fuel burning appliances in the...

Страница 16: ...14 FIGURE 6 0 BOILER INSTALLED IN CONFINED SPACE ALLAIR FROM INSIDE FIGURE 6 1 ALLAIR FROM OUTDOORS VENTILATED CRAWL SPACE AND ATTIC...

Страница 17: ...15 FIGURE 6 2 ALLAIR FROM OUTDOORS VIA VENTILATED ATTIC FIGURE 6 3 ALLAIR FROM OUTDOORS USING OPENINGS INTO BOILER ROOM...

Страница 18: ...rsonal injury or death Do not de rate the appliance Failure to fire the unit at it s designed input may cause excessive condensation upon the interior walls of the chimney In addition the lower input...

Страница 19: ...ystem operating under positive pressure 5 Do not connect the boiler into a chimney flue serving an open fireplace or other solid fuel appliance 6 Prior to boiler installation an existing chimney must...

Страница 20: ...RECOMMENDED BREECHING AND CHIMNEY SIZE BOILER MODEL MINIMUM BREECHING DIA INCHES MINIMUM CHIMNEY REQUIREMENTS ROUND I D IN SQUARE TILE SIZE NOMINAL HEIGHT FT FWZ060 5 6 8 X 8 15 FWZ080 5 6 8 X 8 15 F...

Страница 21: ...ief valve to a location where water or steam will not create a hazard or cause property damage if the valve opens The end of the discharge pipe must terminate in an unthreaded pipe If the relief valve...

Страница 22: ...o the boiler supply just above the boiler with no intervening valves between it and the boiler Use a low water cut off that breaks the 120 VAC supply to the boiler Do not attempt to wire a 24 volt low...

Страница 23: ...21 FIGURE 8 1 INSTALLATION OF FACTORY SUPPLIED PIPING FIGURE 8 2 STANDARD BOILER PIPING...

Страница 24: ...ses above 135 F during the first few minutes of operation A three way valve can be substituted for the two throttling valves shown A bypass can also be used to ensure that the minimum flow requirement...

Страница 25: ...23 FIGURE 8 4 BYPASS PIPING FIGURE 8 5 ISOLATION OF BOILER FROM SYSTEM WITH A HEAT EXCHANGER...

Страница 26: ...ockout problems if the suction line is not completely airtight A two pipe lift system is therefore preferred to a one pipe lift system c TWO PIPE GRAVITY SYSTEM not recommended A vertical distance fro...

Страница 27: ...nufacturer s instructions for tube sizing information 8 Never install manual shut off valves in the return piping of a two pipe system 9 Install a listed flexible oil line s at the burner to facilitat...

Страница 28: ...26 FIGURE 9 2 TWO PIPE GRAVITY FEED SYSTEM NOT RECOMMENDED FIGURE 9 3 TWO PIPE LIFT SYSTEM...

Страница 29: ...d to the 3250 Plus circulator connections or the boiler is provided with a flexible conduit whip that is to be wired to the 3250 Plus circulator connections If the circulator is not already wired to t...

Страница 30: ...ce is present it could destroy the boiler s control One example of an external power source that could be inadvertently connected to the low voltage connections is a transformer in old thermostat wiri...

Страница 31: ...29 FIGURE 10 0 WIRING CONNECTIONS DIAGRAM FOR HYDROSTAT 3250 PLUS CONTROL...

Страница 32: ...30 FIGURE 10 1 CONNECTIONS WIRING DIAGRAM FOR BURNER SPECIFIC PRIMARY CONTROL...

Страница 33: ...rner should fire and flame should be visible through observation port immediately or after prepurge timing has expired if a burner is so equipped Refer to burner instructions for more details 14 Immed...

Страница 34: ...air completely 23 Check thermostat operation by raising or lowering its set point as required cycling burner on and off 24 Verify primary control operation and safety features according to procedure o...

Страница 35: ...E in w c 0 to 0 02 0 to 0 02 0 to 0 02 0 to 0 02 0 to 0 02 0 to 0 02 MAX SMOKE Bacharach Scale 1 1 1 1 1 1 FLUE CO2 MIN MAX 11 5 12 8 11 5 12 8 11 5 12 8 11 5 12 8 11 5 12 8 11 5 12 8 WARNING Attempts...

Страница 36: ...989 50989 51198 STANDARD NOZZLE DANFOSS 0 60 X 60AS HAGO 0 75 X 60B HAGO 1 00 X 45B HAGO 1 35 X 45B INSERTION LENGTH 2 62 2 62 2 62 2 62 PITCH ANGLE 1 1 1 1 PUMP PRESSURE psi 175 175 175 140 HEAD SETT...

Страница 37: ...on FIGURE 12 0 HYDROSTAT 3250 PLUS CONTROL COMPONENT LAYOUT IMPORTANT This boiler is equipped with a feature that saves energy by reducing the boiler water temperature as the heating load decreases Th...

Страница 38: ...ple In a three zone house turn the dial to 2 or 1 Conversely if the boiler provides adequate heat added fuel savings can be achieved by selecting a higher setting example 4 or 5 If the heating and ind...

Страница 39: ...as Pro 2 Turn the HI TEMP dial to select feature 2 3 Push the Test Settings Button to c for Celsius or F for Fahrenheit 1 Reset LO TEMP and HI TEMP settings to desired temperatures see page 28 3 Manu...

Страница 40: ...on the control s Thermal Targeting feature actively sets varying differentials based on system conditions This option allows for selecting a 10 20 or 30 degree fixed differential when the Economy feat...

Страница 41: ...gure 12 3 TABLE 12 2 DEFAULT SETTINGS Dial Setting Feature Options Description Default Setting 1 Thermal Pre Purge Off on Purge Inactive Purge Active Off 2 Fahrenheit or Celsius F c Degrees Fahrenheit...

Страница 42: ...iler temperature drops below the differential set point at which point the boiler will be allowed to fire again See Differential explanation on page 31 NOTE This LED illuminates regularly during norma...

Страница 43: ...and smoke box g Clean the Combustion Chamber Use a wire or fiber bristle brush to clean the surfaces of the combustion chamber Vacuum all loose debris in the chamber h Check condition of the burner s...

Страница 44: ...le with identical make and model see Table 11 1 b Inspect the electrodes Replace if they are deteriorated Make sure that the electrode position is set according to the burner manufacturer s instructio...

Страница 45: ...g sleeved loose fitting clothing 3 Gloves 4 Eye Protection Take steps to assure adequate ventilation Wash all exposed body areas gently with soap and water after contact Wash work clothes separately f...

Страница 46: ...g in odor complaints 6 Dirt The use of a fuel filter is good practice Accidental accumulation of dirt in the fuel system can clog the nozzle or nozzle strainer and produce a poor spray pattern from th...

Страница 47: ...al this table and flow charts assume that there are no loose or miswired electrical connections Before using these tables inspect all electrical connections on the boiler to make sure that they are ti...

Страница 48: ...ith the inside of the well tube Check that the well does not have excessive build up of heat transfer grease that may interfere with the clip contacting the well 2 Remove well and examine for excessiv...

Страница 49: ...Temp Active LED will be on at all times when the control is powered Check for 120 VAC on terminals L1 and L2 YES Is the Red LED LOW WATER On YES NO Is the Yellow LED HI TEMP On YES The Control is Sen...

Страница 50: ...echeck wiring Make sure that burner is wired to B1 Burner should never fire when red or yellow LED is lit Is either Yellow LED On The Control has Reached Target or High Limit Temperature The Control i...

Страница 51: ...TS 410023 1 11 1 2 DIA ROPE GASKET SWING DOOR 410024 1 1 1 1 1 1 12 1 8 DIA ROPE GASKET OBSERVATION PORT 410032 1 1 1 1 1 1 13 OBSERVATION PORT COVER 410022 1 1 1 1 1 1 14 SOCKET HD CAP SCREW 5 16 18...

Страница 52: ...50...

Страница 53: ...1 1 1 34 TOP JACKET PANEL 1 410322 410322 410323 410323 410324 410325 35 FIBERGLASS INSULATION WRAPPER 1 412302 412302 412303 412303 412304 412305 36 POWER RECEPTACLE 960041 1 1 1 1 1 1 37 CROWN NAME...

Страница 54: ...0117 1 1 1 1 1 1 59 3 4 NPT DRAIN VALVE 95 041 1 1 1 1 1 1 61 1 1 2 NPT X 8 NIPPLE 950028 1 1 1 1 1 1 62 1 1 2 NPT CROSS 950029 1 1 1 1 1 1 63 1 1 2 NPT PLUG 95 143 1 1 1 1 1 1 64 1 1 2 X 3 4 BUSHING...

Страница 55: ...53...

Страница 56: ...Manufacturer of Hydronic Heating Products P O Box 14818 3633 I Street Philadelphia PA 19134 www crownboiler com...

Отзывы: