Crowcon Flamgard-4/20 Скачать руководство пользователя страница 3

3. OPERATION

2. INSTALLATION (continued)

NOTES

WARNING

Prior to carrying out any work ensure local regulations and site

procedures are followed.

Never attempt to open the detector or junction box when

flammable gas is present.

Ensure that the associated control panel is inhibited so as to

prevent false alarms.

3.1 Commissioning procedure

The following procedure should be followed carefully, and carried out

only by suitably trained personnel:

a.

Open the junction box of the detector by removing the 4 M6 Allen

head screws.

b.

Check that all electrical connections have been made and are

correct as per Diagram 3.

c.

Apply power to the detector and ensure the minimum supply voltage

of 10 V dc is available at the detector across terminal ‘+’ and ‘-’.

d.

Leave the detector to stabilise for 1 -2 hours.

e.

Connect a digital volt meter (DVM) to the test points on the amplifier

in the junction box. Note : The test points read 40 mV = 4 mA = 0%

up to 200 mV = 20 mA = 100% LEL gas. There is a current clamp of

25 mA on the 4-20 mA output.

f.

With no flammable gas present at the detector adjust the ‘ZERO’ pot

on the amplifier until the DVM reads 40 mV.

g.

Apply calibration gas to the detector at a flow rate of 0.5 litres per

minute. Crowcon recommend 50% LEL gas for calibration purposes

(contact Crowcon for the supply of calibration gas).

h.

Allow the gas reading to stabilise and adjust the ‘CAL’ pot until the

DVM reads the appropriate reading (120 mV = 50% LEL if used).

i.

If the control equipment display requires adjustment consult the

operating manual for the equipment.

a.

Switch off and isolate power to the detector requiring attention.

b.

Open the junction box by unscrewing the 4 M6 Allen head screws.

c.

Disconnect the 3 sensor wires from the terminal block of the

amplifier.

d.

Unscrew the complete 96HD sensor housing from the junction box.

e.

Open the 96HD sensor housing by removing the four Allen head

screws from the Top Cap with a 3mm Allen Key.

f.

Remove the sensor from the Top Cap PCB. Flammable sensors have

an extra black sleeve which may be seperate from the sensor. This

is normal and the sleeve may be re-used.

g.

Fit the replacement sensor checking the part number is correct. This

part number is labelled on the main body of the detector. Observe

pin alignment with PCB.

h.

Inspect the gaskets and replace if necessary.

i.

The sinter assembly will only need to be replaced if it has become

blocked by dust or oil. Such blockages cause the response time of

the detector to be slow and may affect sensitivity. To remove the

sinter a removal tool (Part No. M01614) is required. Loctite No 243

must be used on sinter assembly threads to maintain certification.

j.

Re-assemble the 96HD housing taking time to ensure that the four

Allen head screws are securely fixed into position.

k.

Fit the 96HD sensor housing to the junction box ensuring that the

colour coded wires are terminated correctly.

l.

Remove the amplifier fixing screws and rear lid.

m.

Connect a DVM to TP2 on the amplifier PCB.

n.

Switch on power and adjust VR3 until DVM reads 0 mV.

o.

Re-assemble the amplifier.

p.

Follow the Commissioning Procedure given in 3.1 above.

If a spare 96HD sensor housing complete with new sensor is

available, ignore steps (e.) to (j.) and return the old 96HD to Crowcon or

an approved service centre for repair.

j.

Close the junction box of the detector ensuring the 4 x M6 Allen head

screws are securely fastened.

k.

The detector is now operational.

3.2 Routine maintenance

The operational life of the pellistor sensor depends on the application.

Crowcon expect that such a device will work satisfactorily for up to 5

years in ideal conditions. Site practices will dictate the frequency with

which detectors are tested. Crowcon recommends that detectors be gas

tested at least every 6 months and re-calibrated as necessary. To re-

calibrate a detector follow steps 3.1 (a.), (e.) to (k.) above.

Pellistors can suffer from loss of sensitivity when there is a

presence of poisons or inhibitors such as silicones, sulphides, chlorine,

lead or halogenated hydrocarbons. Crowcon use poison resistant

pellistors to maximise the operational life of Flamgard-4/20. In

applications where such compounds are present continuously we

recommend the use of CIRRUS or NIMBUS, Crowcon’s fixed point

infrared flammable gas detectors, which are immune to such poisons

and inhibitors. Please contact Crowcon for further details.

3.3 Sensor replacement/servicing of detectors

WARNING

This work should be carried out by Crowcon or an approved

service centre unless suitable training has been received.

Flamgard 4/20 uses the 96HD sensor housing which allows the user to

replace the sensors, gaskets and sinter if necessary. An exploded view

of the 96HD sensor housing is given in Diagram 2 for reference. The

following procedure may be followed when servicing the detector:

Area Classifications:-

Zone 0:

An area classified, as Zone 0 will have ignitable 

concentrations of flammable gases, vapours or 

liquids present continuously or for long periods of 

time under normal operating conditions.

Zone 1:

An area classified, as Zone 1 is likely to have 

ignitable concentrations of flammable gases, 

vapours or liquids present under normal operating 

conditions.

Zone 2:

An area classified, as Zone 2 is not likely to have 

ignitable concentrations of flammable gases, 

vapours or liquids present under normal operating 

conditions.

Dimensions

190 x 129 x 85 mm (7.3 x 5 x 3.4 inches)

Weight

4.0 kg (8.8 lbs)

Operating voltage

10-30 V dc

Current consumption

140 mA @ 10 V, 50mA @24V

Operating temperature

-10-55

O

C

Humidity

0-99% RH, non condensing

Cable loop resistance

60 Ohm @ 22 V +ve terminal (power)
600 Ohm @ 22 V signal terminal (4-20 mA)

Degree of protection

IP66 (when fitted with Weatherproof Cap)

Explosive protection

Flameproof

Approval code

II 2 G EEx d IIC T6

Safety certification no.

Amplifier unit (Junction Box): 

Baseefa03ATEX0074 

96HD: Sira02ATEX1283X

Standards

EN50014, EN50018

Zones

Certified for use in Zone 1 or Zone 2 areas. 

(see area classifications section)

Gas groups

IIA, IIB, IIC

EMC

EN50270

Detector output

Source or sink selected by internal switch

Description

Part Number

M20 to 1/2” NPTF adaptor

M02125

M20 to 3/4” NPTF adaptor

M02281

Ceiling mounting bracket

M01401

Collector cone

C01051

Spray deflector

C01338

Swivel mounting bracket

C01340

96HD sensor housing complete with sensor

S01749*

1

Replacement sensor

S01673*

1

Sinter removal tool

M01 614

Loctite No. 243

Sinter assembly

S01781

Gasket 1

M04452

Gasket 2

M04128

Calibration gas

Contact Crowcon

*1

Flamgard 4/20 may be fitted with a range of pellistor sensors depending on the
specific application. The correct spare sensor part number is itemised on the
sensor housing label

.

4. SPARE PARTS AND ACCESSORIES

5. SPECIFICATION

7

8

9

10

11

12

Diagram 3: 

Electrical connections

Отзывы: