INSTALLATION MANUAL

NTR 756 D / e

09/2003- 3/13

Содержание MILLENIUM II+ Series

Страница 1: ...LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 D E ...

Страница 2: ...nd actuators in the installation A display on the front panel allows you to check the status of your system at any time The MILLENIUM II series features Simple programming and parameter setting WINDOWS based programming software Compact size EEPROM module backup Real time clock as standard Output with high switching capacity The MILLENIUM II series is ideal for simple automation systems examples l...

Страница 3: ... 12 S 88 950 026 SA 12 S 88 950 046 12 VDC 12 VDC 8 TRANSISTOR 4 72 x 90 x 60 250 EC 20 R 88 950 033 SA 20 R 88 950 053 EX 20 R 88 950 833 XT 20 R 88 950 063 100 240 VAC 100 240 VAC 12 RELAY 8 EC 20 R 88 950 034 SA 20 R 88 950 054 XT 20 R 88 950 064 EX 20 R 88 950 834 24 VAC 24 VAC 12 RELAY 8 EC 20 R 88 950 031 SA 20 R 88 950 051 XT 20 R 88 950 061 EX 20 R 88 950 831 24 VDC 24 VDC 12 RELAY 8 EC 20...

Страница 4: ...INSTALLATION MANUAL NTR 756 D e 09 2003 3 13 ...

Страница 5: ...6 A 3 5 W 4 W 1 ms 12 VDC 15 30 XT20R 12VDC 11 30 6 A 2 2 W 4 5 W 1 ms 2 3 Description of inputs n 100 240 VAC 24 VAC Description Description of AC inputs Input voltage 100 240 VAC 15 10 24 VAC 15 10 Operating frequency 50 60 Hz 50 60 Hz Current consumption 0 35 mA typical 0 4 mA max 6 2 mA typical 7 5 mA max Input impedance 700 KΩ 4 KΩ sauf 88 950 835 120 kΩ pour I1 I2 I3 I4 Level 0 40 VAC 5 VAC ...

Страница 6: ... isolation No Status indication LCD display Description Description of analogue inputs 12 I O I 05 I 08 20 I O I 05 I 12 Number of bits 8 Resolution 10 000 250 mV Conversion time 10 ms Input voltage 0 10 VDC Input impedance 22 KΩ Precision 5 Default Offset Gain Offset 0 Gain 1 These values can be altered via the software Temperature drift 3 LSB over the authorized range Response time 10 ms Galvani...

Страница 7: ... isolation No Status indication LCD display Description Description of analogue inputs 12 I O I 05 I 08 20 I O I 05 I 12 Number of bits 8 Resolution 10 000 250 mV Conversion time 10 ms Input voltage 0 10 VDC Input impedance 10 KΩ 14 K typical Precision 5 Default Offset Gain Offset 0 Gain 1 These values can be altered via the software Temperature drift 3 LSB over the authorized range Response time ...

Страница 8: ...C12 resistive 250 VAC 2000 VA 100 000 1800 DC12 resistive 30 VDC 192 W 100 000 1800 2 5 Description of transistor outputs Description Description of transistor outputs Operating voltage 5 24 VDC 20 Maximum current 0 7 A Minimum load 1 mA Maximum inductive and resistive loads 0 7 A 24 VDC 24 W Maximum ignition load 0 125 A 24 VDC 3 W Ton Toff Toff Ton response time 1 ms Leakage current 0 1 mA 24 VD...

Страница 9: ...INSTALLATION MANUAL NTR 756 D e 09 2003 8 13 LCD display Display with 4 lines of 12 characters ...

Страница 10: ...outputs Between the terminals and the DIN 43880 or equivalent control unit Insulation resistance IEC EN 60730 1 IEC EN 60601 1 2 MΩ at 500 VDC between the following points Power supply terminals I O terminals Between the relay outputs Between the terminals and the DIN 43880 or equivalent control unit Impulse voltage IEC EN 60947 1 IEC EN 60730 1 IEC EN 60664 1 230 VAC version 4 KV 24 VDC version 0...

Страница 11: ... or mounting in a DIN 43 880 box 3 2 Panel mounting Recommended fixing screw diameter M4 3 3 Screw terminal connection The end of the wire should be fitted with a ferrule Ref Description of front panel 1 Fixing holes 2 Power supply screw terminal 3 LCD display 4 Input screw terminal 5 Escape key 6 Slot for memory module or PC cable 7 Scroll buttons 8 Selection button 9 Output screw terminal ...

Страница 12: ...xcessive shock or vibration Do not install the module in water or near any possible leaks Protect the module from external debris during installation Keep as far away as possible from power cables and equipment The MILLENIUM II series module can be installed in enclosures complying with standard DIN 43880 To ensure adequate module ventilation there should be a gap of 10 mm between the front panel ...

Страница 13: ...INSTALLATION MANUAL NTR 756 D e 09 2003 12 13 ...

Страница 14: ...5 mm 26 14 AWG Strip the conductor over a length of 7 0 5 mm Unscrew the terminal screw to its maximum before inserting the conductor Insert the wire fully into the terminal and screw tight to ensure correct connection Maximum tightening 0 5 Nm 5kgfcm Do not coat the conductors with tin to prevent them breaking 4 3 Power supply For an AC power supply the phase should be connected to the L terminal...

Страница 15: ...erature 5 C 55 C Terminals L and N cannot be reversed 1 fuse or cut out POWER DC INPUT DC 24 VDC 15 20 12 VDC 15 30 EX XT20R 12VDC 11 30 Ambient temperature 5 C 55 C 10 KΩ max 2 2 KΩ 0 5W optimum value See local extension manual SA EC CN 12 SA EC CN 20 EX XT 20 L N 1 1 SA EC CN 12 SA EC CN 20 EX XT 20 24VDC 12 VDC See local extension manual ...

Страница 16: ... MANUAL NTR 756 D e 09 2003 15 13 4 5 Output wiring diagram OUTPUT RELAY Resistive load 8A 250 VAC 30 VDC OUTPUT TRANSISTOR 5 28 8 VDC 0 7A max SA EC CN 12R ou SA EC EX XT CN 20R ou SA EC CN 12S SA EC EX XT CN 20S ...

Страница 17: ...elow to emphasize information relating to the safety of persons and protection of equipment When these symbols are encountered the associated annotation should be read and fully understood The symbols are Under no circumstances can Crouzet be held responsible for damage resulting from installation or use of this equipment All examples and diagrams in this manual are intended to assist understandin...