13
FnIO G-Series
Copyright(C)CREVIS Co.,Ltd S82-31-899-4599 URL: www.crevis.co.kr
123.4usec (*3)
- Aph Input acts as Pulse Input
- Bph Input is not used
B' 1111 ( 0xF )
Pulse Width & Period
Measurement
Simple Pulse Width & Period Measurement, 0.1usec Unit,
- Available in case of Pulse Input >= 200Hz(<= 2.5msec,
Pulse On Width)
- Pulse Width(16bit, Low Word) + Pulse Period(16bit, High
Word) (*4)
- Aph Input acts as Pulse Input
- Bph Input is not used
- This encoder mode is perfectly same with mode B'0000, B'0001. This is for using Encoder module easily.
- Frequency, B'1100(0xC) and B'1101(0xD) can't be used with other channel's Count Mode = 0x2 ~ 0x9
- Pulse Width, B'1110(0xE) measures Aph Input's High(On) Pulse Width(32bit) in 0.1usec unit.
- Pulse Width & Period, B'1111(0xF)measures Aph's Pulse High(On) Width(16bit) & Period(16bit) in 0.1usec
unit.
2.1.6. Configuration Parameter Data – 4byte
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Reserved
1
Reserved
2
Reserved
3
Reserved