4. Name of each Part
3
4
5
Status LED Window(refer to the
description below)
EtherNet Connector
Serial Communication Connector
( For manufacturer use only)
Latch for DIN Rail
*1
Description for LED status
2
Removable Terminal Block
6
MAC ID
Item
LED is:
State
To indicate:
MOD :
Module
Status LED
Off
No Power
No power is supplied to the unit.
Green
Device Operational
The unit is operating in normal condition.
Flashing
Green
Device in Standby
The device needs commissioning due to configuration
missing, incomplete or incorrect.
Flashing Red
Minor Fault
Recoverable Fault
- EEPROM sum check error.
Red
Unrecoverable Fault
The device has an unrecoverable fault.
- Memory error or CPU watchdog error.
NET :
Network
Status LED
Off
Not Powered
No IP Address
Module is not powered.
Does not have an IP address
Flashing
Green
No Connections
Module has obtained an IP address, but has no
Established connections.
Green
CIP Connections
Module has an IP address and at least one established
connections.
Flashing
Red
Connection Time-out
One or more of the connections in which the module is
The target has time out.
Red
Duplicate IP Address
Module has detected that its IP address is already in use.
Configure the module with a unique IP address.
LINK :
Link/Active
Status LED
Off
Not Powered
Physical network not
ready
May not be powered
Green
Link Operational
Physical Network communication ready
Flashing
Green
Act Operational
some data communication on the base Ethernet 802.3
I/O :
IO Module
Status LED
Off
Not Powered
No
IO
Module
Device has no
IO
module or may not be powered
Flashing
Green
FnBus On-line,
Do not Exchanging I/O
FnBus is normal but does not exchanging I/O data
(Passed the
IO
module configuration).
Green
FnBus Connection,
Run Exchanging IO
Exchanging I/O data
Flashing
Red
FnBus connection fault
during exchanging IO
One or more
IO
module occurred in fault state.
- Changed
IO
module configuration.
- FnBus communication failure.
Red
Expansion
Configuration
Failed
Failed to initialize
IO
module
- Detected invalid
IO
module ID.
- Overflowed Input / Output Size
- Too many
IO
module
- Initial protocol failure
Field Power
Status LED
Off
Not Supplied Field
Power
Not supplied 24Vdc field power
Green
Supplied Field Power Supplied 24Vdc field power