3.6.4 Environment Specification
Environmental specification
Operation Temperature
-40
℃
to 70
℃
Non-Operating Temperature
-40
℃
to 85
℃
Relative Humidity
5% to 95% Non-condensing
Operating Altitude
2,000m
General specification
General specification
Shock Operating
IEC 60068-2-27
Vibration Resistance
Based on IEC 60068-2-6
Sine Vibration
- 5 ~ 25Hz : ±1.6mm
- 25 ~ 300Hz : 4g
- Sweep Rate : 1 Oct/min, 20 cycles
Random Vibration
- 10 ~ 40 Hz : 0.0125 g
2
/Hz
- 40 ~ 100 Hz : 0.0125 → 0.002 g
2
/Hz
- 100 ~ 500 Hz : 0.002 g
2
/Hz
- 500 ~ 2000 Hz : 0.002 → 1.3 x 10
-4
g
2
/Hz
- Test time : 1hrs for each test
Industrial Emissions
EN 61000-6-4 : 2007+A1:2011
Industrial Immunity
EN 61000-6-2 : 2005
Installation Position
Vertical and horizontal installation is available.
Product Certifications
CE, UL