Description

The Crestron

®

 junction box-mounted zone controllers deliver intelligent lighting control 

with essential features for energy efficiency. Available for 20 A switching, 5 A or 16 A 
0-10 V dimming, and 20 A plug load control, each ZUMMESH-JBOX model wirelessly 
connects to Z

ū

m daylight sensors, occupancy sensors, vacancy sensors, keypads, and 

dimmers (all sold separately) over the Z

ū

m mesh network, providing intelligent lighting 

control based on the amount of natural light and the presence of people in a space. The 
Z

ū

m J-Box Zone Controllers offer a powerful lighting control solution for every space 

within the Z

ū

m network.

A basic single-room Z

ū

m system consists of Z

ū

m mesh devices, i.e., dimmers, switches, 

keypads, and sensors. The Z

ū

m mesh devices in the room communicate directly with 

each other without the need for a centralized gateway or processor.
To monitor or control the room from a centralized Crestron control system, use the 
ZUMMESH-NETBRIDGE.

NOTE

:  The ZUMMESH-NETBRIDGE requires a J-box device to provide power.

For quick network setup, use the Z

ū

m app on a smartphone or tablet.

Additional Resources

Visit the product page on the Crestron website (www.crestron.com) 
for additional information. Use a QR reader application on your 
mobile device to scan the QR image.

Installation

WARNING

:  To avoid fire, shock, or death, turn off the power at the circuit breaker or 

fuse and test that the power is off before wiring! 

NOTES

:  Observe the following points:

  •  Install and use this product in accordance with appropriate electrical codes and 

regulations.

  •  A licensed electrician should install this product.
To install a switch or dimmer, do the following:
  1.  Turn the power off at the circuit breaker.
  3.  Mount the J-box device to the J-box.
  2.  Wire the device as shown in the following diagrams.

ZUMMESH-JBOX-5A-LV, ZUMMESH-JBOX-16A-LV, 
and ZUMMESH-JBOX-20A-SW Wiring

Test the Loads

Press the TEST button to toggle the connected loads. 
Press and hold the TEST button to cycle dim the connected loads (dimmer models only).

ZUMMESH-JBOX-PSU Wiring

NOTE

:  The 0–10 V dim - and 0–10 V dim + wires are not present on the 

ZUMMESH-JBOX-20A-SW.

ZUMMESH-JBOX-20A-PLUG Wiring

SPECIFICATION 

DETAILS 

Power Requirements 

 

  Line Power 

100-277 Vac, 50/60 Hz 

  Idle State Power 

Consumption 

1 W 

Expansion Port 

Expansion port allows connection of an 
accessory such as a Z

ū

m Network Bridge 

(ZUMMESH-NETBRIDGE) or HVAC Contact 

Closure Module (ZUM-CCO) 

Models 

 

  ZUMMESH-JBOX-16A-LV / 

ZUMMESH-JBOX-5A-LV 

 

     Switched Output 
 

16 A at 100-277 Vac, 50/60 Hz (20 A, de-rated  
to 80%) 

5 A at 100-277 Vac, 50/60 Hz 

     0-10V Output 

60 mA Sink or Source 

     DIM Load Type 

LED driver (4-wire), Fluorescent, Incandescent, 
MLV, ELV 

     Functionality 

Controlled by keypads, occupancy or vacancy, 

and daylight sensors. 

     Expansion Port 

Allows connection of Z

ū

m Network Bridge or 

Relay Contact Closure Module 

  ZUMMESH-JBOX-20A-SW 

 

     Switched output 

 

20 A high in-rush (de-rated to 80%), zero cross 
switching 

     Switch Load Types 

0-10 V LED driver, Fluorescent ballast (4-wire), 60 
mA max current sink or source 

     Functionality: 

Controlled by keypads and occupancy or 
vacancy sensors 

     Expansion Port: 

Allows connection of Z

ū

m Network Bridge or 

Relay Contact Closure Module 

ZUMMESH-JBOX-20A-PLUG 

 

     Switched output 

20 A high in-rush, zero cross switching for control 

of receptacles 

     Functionality 

Controlled by occupancy or vacancy sensors to 
energize receptacles when the room is occupied. 
Note that the output defaults to energized state 

after a power cycle. 

     Expansion Port 

Allows connection of Z

ū

m Network Bridge or 

Relay Contact Closure Module 

  ZUMMESH-JBOX-PSU 

 

     Functionality 

Provides power for Z

ū

m Network Bridge when 

other J-box devices are not available. 

     Expansion Port 

Allows connection of Z

ū

m Network Bridge or 

Relay Contact Closure Module 

Enclosure 

 

  Housing 

Plastic, white, UL

®

 standard 5VA rated 

  Mounting 

Mounts in a 4˝ x 4˝ junction box via 1/2 in conduit 
knockout;  
Rated for mounting in plenum spaces, UL 

standard 2043 

Environmental 

 

  Temperature 

32° to 104 °F (0° to 40 °C) 

  Humidity 

10% to 90% RH (noncondensing) 

Dimensions 

 

  Height 

3.25 in (83 mm) 

  Width 

4.17 in (106 mm) 

  Depth 

1.31 in (33 mm) 

Weight 

0.4 lbs (7 oz) 

 

Neutral (white)

To 0-10 V 

Controlled load

0-10 V dim + (purple)

0-10 V dim - (gray)

Switched output (red)

Neutral

(white)

Hot (black)

100-277 Vac power 

from breaker

Neutral (white)

15 or 20 A receptacle

Switched output (red)
Hot (black) to 

unswitched 

receptacles

Neutral (white)

Hot (black)

100-277 Vac power 

from breaker

Neutral (white)

Hot (black)

100-277 Vac power 

from breaker

Отзывы: