Crestron
DIN-HUB
DIN Rail Cresnet
®
Distribution Hub
Setup
Network Wiring
When wiring the Cresnet
®
network, consider the following:
•
Use Crestron Certified Wire.
NOTE:
Cresnet-HP wire cannot be used.
•
Use Crestron power supplies for Crestron equipment.
•
Provide sufficient power to the system.
CAUTION:
Insufficient power can lead to unpredictable results
or damage to the equipment. Please use the Crestron Power
Calculator to help calculate how much power is needed for the
system (
).
For more details, refer to “Check Network Wiring” on page 14.
Installation
The DIN-HUB must be installed by a licensed electrician, in accordance
with all national and local codes.
CAUTION:
This equipment is for indoor use only. Mount in a well
ventilated area. The ambient temperature must be 0º to 40º C
(32º to 104º F). The relative humidity must be 10% – 90%
(non-condensing).
Operations & Installation Guide – DOC. 6671A
DIN Rail Cresnet Hub: DIN-HUB
•