background image

Crestron Green Light™ 

DIN-HUB 

DIN Rail Cresnet

®

 Distribution Hub 

Operations & Installation Guide 

 

Содержание Green Light DIN-HUB

Страница 1: ...Crestron Green Light DIN HUB DINRailCresnet DistributionHub Operations Installation Guide ...

Страница 2: ...n by the Technical Documentation department at Crestron Electronics Inc 15 Volvo Drive Rockleigh NJ 07647 1 888 CRESTRON All brand names product names and trademarks are the property of their respective owners 2008 Crestron Electronics Inc ...

Страница 3: ...ications 4 Physical Description 5 Industry Compliance 8 Setup 9 Network Wiring 9 Installation 9 Hardware Hookup 11 Problem Solving 13 Troubleshooting 13 Check Network Wiring 14 Reference Documents 15 Further Inquiries 16 Future Updates 16 Return and Warranty Policies 17 Merchandise Returns Repair Service 17 CRESTRON Limited Warranty 17 Operations Installation Guide DOC 6671A Contents i ...

Страница 4: ......

Страница 5: ...ail lighting and automation control modules and other third party DIN rail mountable devices Features and Functions Three segment Cresnet hub Recommended for large Cresnet networks Configurable power distribution No programming required 6M wide DIN rail mounting Use of a DIN HUB is advised whenever the number of Cresnet devices on a network is greater than 20 or when the combined total length of C...

Страница 6: ...he maximum number of possible devices on a complete Cresnet network Contact Crestron True Blue Support www crestron com true_blue_support for further design assistance Cresnet Power Distribution In addition to data Cresnet carries 24 Volts DC for powering the devices connected to it The DIN HUB provides an easy way to manage the distribution of power for a complete Cresnet network Each segment can...

Страница 7: ...UB DIN Rail Cresnet Distribution Hub Applications The following diagram shows a DIN HUB in a typical application DIN HUB in a Typical Application Operations Installation Guide DOC 6671A DIN Rail Cresnet Hub DIN HUB 3 ...

Страница 8: ... 40 C 32 to 104 F 10 to 90 RH non condensing 2 BTU Hr Enclosure Light gray polycarbonate housing with polycarbonate label overlay UL94 V 0 rated 35 mm DIN EN 60715 rail mount DIN 43880 form factor for enclosures with 45 mm front panel cutout occupies 6 DIN module spaces 108 mm Dimensions Height Width Depth 94 2 mm 3 71 in 106 mm 4 17 in 58 0 mm 2 28 in Weight 155 g 5 oz Available Accessories DIN B...

Страница 9: ...ction provides information on the connections controls and indicators available on your DIN HUB DIN HUB Physical View DIN HUB Overall Dimensions 106 mm 4 17 in 94 2 mm 3 71 in 90 mm 3 54 in 58 mm 2 28 in 1 2 3 Operations Installation Guide DOC 6671A DIN Rail Cresnet Hub DIN HUB 5 ...

Страница 10: ...A B C ports Max Wire Size 1 5 mm2 16 AWG Maximum Load per Segment 75 Watts 3 13 Amps 24 Volts DC 2 NET HOST and LEDs 2 4 pin 3 5 mm detachable terminal blocks paralleled Connects to Master NET port of DIN AP2 or other control system and loops through to additional DIN Rail Cresnet devices Max Wire Size 1 5 mm2 16 AWG Pin 1 24 Power 24 VDC Pin 2 Y Data Pin 3 Z Data Pin 4 G Ground 1 Green LED indica...

Страница 11: ...blocks comprising 2 Cresnet ports paralleled per each of 3 segments Max Wire Size 1 5 mm2 16 AWG 3 Green LEDs indicate Cresnet power is available at NET ports of corresponding hub segment 3 Yellow LEDs indicate Cresnet bus activity at NET ports of corresponding hub segment 1 Interface connectors for NET HOST NET PWR INPUT and NET ports are provided with the unit 2 Y Z and G terminals are parallele...

Страница 12: ...s These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installatio...

Страница 13: ...ment Please use the Crestron Power Calculator to help calculate how much power is needed for the system www crestron com calculators For more details refer to Check Network Wiring on page 14 Installation The DIN HUB must be installed by a licensed electrician in accordance with all national and local codes CAUTION This equipment is for indoor use only Mount in a well ventilated area The ambient te...

Страница 14: ...ducts it may be necessary to use a flat head screw driver to pull the DIN rail release tab while snapping the device onto the DIN rail To remove the DIN HUB from the DIN rail use a small flat object i e a flat head screwdriver to pull the DIN rail release tab and tilt the bottom of the DIN HUB away from the DIN rail NOTE Certain third party DIN cabinets provide space for an informational label bet...

Страница 15: ...s have been made When making connections to the DIN HUB use a Crestron power supply Hardware Connections for the DIN HUB NET TO CONTROL SYSTEM AND OTHER CRESNET DEVICES NET PWR INPUT 24 VDC JUMPERED FROM NET HOST PORT or EXTERNAL SUPPLY EACH PORT PROVIDES POWER TO A SEGMENT NET B CONNECT TO CRESNET DEVICES ON SEGMENT B NET A CONNECT TO CRESNET DEVICES ON SEGMENT A NET C CONNECT TO CRESNET DEVICES ...

Страница 16: ...ices that are connected to any of the segments Hub segments can be powered internally or from an external power supply like the DIN PWS50 To power a segment internally install a jumper from the HOST pin to the EXT pin on the segment s NET PWR INPUT port as shown in the following diagram Powering a Hub Segment Internally Segment A Shown To power a segment externally connect the external power suppl...

Страница 17: ...UB is properly connected to a Cresnet power supply Segment is improperly wired Verify wiring connections proper connector is used cable in intact and connections are secure Device s attached to segment is not properly identified in SIMPL Windows Use Crestron Toolbox to verify that the SIMPL Windows program recognizes all of the devices Segment s NET LED does not illuminate Other segment is imprope...

Страница 18: ...ron Certified Wire and only Crestron Certified Wire may be used Failure to do so may incur additional charges if support is required to identify performance deficiencies because of using improper wire Calculate Power CAUTION Use only Crestron power supplies for Crestron equipment Failure to do so could cause equipment damage or void the Crestron warranty CAUTION Provide sufficient power to the sys...

Страница 19: ...awing 20 watts should not have a length of run more than 101 meters 333 feet Cresnet HP cannot be used NOTE All Crestron certified Cresnet wiring must consist of two twisted pairs One twisted pair is the 24V conductor and the GND conductor and the other twisted pair is the Y conductor and the Z conductor Strip and Tin Wire When daisy chaining Cresnet units strip the ends of the wires carefully to ...

Страница 20: ...p to ask questions about Crestron products First time users will need to establish a user account to fully benefit from all available features Future Updates As Crestron improves functions adds new features and extends the capabilities of the DIN HUB additional information may be made available as manual updates These updates are solely electronic and serve as intermediary supplements prior to the...

Страница 21: ...or 90 days batteries and incandescent lamps are not covered This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer Purchasers should inquire of the dealer regarding the nature and extent of the dealer s warranty if any CRESTRON shall not be liable to honor the terms of this warranty if the product has been used in any application other than that for whi...

Страница 22: ...DIN Rail Cresnet Distribution Hub Crestron DIN HUB 18 DIN Rail Cresnet Hub DIN HUB Operations Installation Guide DOC 6671A This page is intentionally left blank ...