Clearing out the DIN-DALI-2 Internal Memory
If addresses of ballasts are changed via console commands or if ballasts are removed
or replaced during the commissioning phase, the internal copy of ballast settings may
not match what is installed. Typically the internal memory retains the previous
settings for a ballast and then shows the new settings as a new ballast. The status list
shows a ballast with the previous address as missing and a ballast with the new
settings as new.
If this occurs, the internal memory in the DIN-DALI-2 should be cleared and the
latest settings read back in from the ballasts. Both can be achieved using the software
tool.
To clear internal memory, go to the DALI Commissioning Tool in Crestron Toolbox,
click
Setup
, and select
Clear Commission Settings
.
To read back ballast info (what ballasts are on the network and all their parameters),
go to the DALI Commissioning Tool in Crestron Toolbox, click
Setup
and select
Replace DIN-DALI-2 settings with ballast settings
.
The DIN-DALI-2 should now show only the ballasts that are physically present.
It is important that internal memory matches what is stored in the ballasts so that
future ballast replacement can take place without recommissioning the system.