Crestron 

CLW-DELVEX-E/P

Wireless In-Wall Dimmer

Installation Guide

This product conforms to UL STD 1472; certified to CSA STD C22.2 No. 184.1.

FCC ID: Contains EROCWD6790
Compliance Statement (Part 15.19 )

This device complies with Part 15 of the FCC Rules. Operation is subject to the following 

two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may 

cause undesired operation.

Warning (Part 15.21)

Changes or modifications not expressly approved by the party responsible for 

compliance could void the user’s authority to operate the equipment.

RF Exposure (OET Bulletin 65)

To comply with FCC's RF exposure limits for general population / uncontrolled exposure, 

this transmitter must be installed to provide a separation distance of at least 20 cm from 

all persons and must not be co-located or operating in conjunction with any other 

antenna or transmitter.

DESCRIPTION

The CLW-DELVEX-E/P is a 500 W in-wall dimmer and programmable keypad designed to 

operate as part of a complete Crestron

®

 automation system communicating via the 

infiNET EX

®

 wireless control network. Without the need for additional control wiring, the 

CLW-DELVEX-E/P easily replaces any standard in-wall dimmer or light switch. Although 

functional as a standalone dimmer, the CLW-DELVEX-E/P delivers enhanced automation 

and control capability when connected to any Crestron automation control system (or any 

other Creston control system) via the infiNET EX network.

Specifications

Specifications for the CLW-DELVEX-E/P are listed in the following table.

CLW-DELVEX-E/P Specifications

  3.  Push all power wires back into the electrical box and fasten the device to the electrical 

box with the provided screws.

  4.  Attach decorative faceplate.
  5.  Ensure all buttons, including the program button, actuate without sticking.
  6.  Restore power at the circuit breaker. 

Multigang Installations

In multigang installations, several devices are grouped horizontally in one electrical box. For 

a smooth appearance, one-piece multigang faceplates (not supplied) can be installed.

NOTE

:  When installing into a multigang box, do not fully tighten devices to box until 

faceplate has been aligned.

The load capacity for each device in the electrical box must be derated. Refer to the 

following diagrams for derating information.

Derating Information for CLW-DELVEX-E/P Dimmers

1.  CLW-DELVEX-P only.
2.  For details, refer to the Crestron CLW-SLVU-P Installation Guide (Doc. 7364) at 

www.crestron.com/manuals.

1.  CLW-DELVEX-P only.

2.  The range is dependent on its placement and the building in which it is used. The construction of the building, 

obstructions, and RF interference from other devices are factors determining the effective range of the unit.

Important Notes

Read before installation.

 

 

Codes: Install in accordance with all local and national electrical codes.

CAUTION

:  TO REDUCE THE RISK OF OVERHEATING AND POSSIBLE DAMAGE 

TO OTHER EQUIPMENT, DO NOT INSTALL TO CONTROL A RECEPTACLE, A 

MOTOR-OPERATED APPLIANCE OR TRANSFORMER-SUPPLIED APPLIANCE.

ATTENTION

: GRADATEURS COMMANDANT UN BALLAST-AFIN DE RÉDUIRE 

LE RISQUE DE SURCHAUFFE ET LA  POSSIBILITÉ  D’ENDOMMAGEMENT À 

D’AUTRES MATÉRIELS,  NE PAS INSTALLER POUR COMMANDER UNE PRISE,  

UN APPAREIL OPÉRÉ DE MOTEUR OU UN APPAREIL ALIMENTÉ PAR UN 

TRANSFORMATEUR.

 

 

Wiring: Use copper wire only. For supply connections, use wire rated for at least 75° C.

 

 

Lamp Type: For use with permanently installed incandescent, electronic low voltage 

halogen or LED, tungsten-halogen, or dimmable CFL only.

 

 

Electrical Boxes: Devices mount in standard electrical boxes. For easy installation, 

Crestron recommends using 3 1/2 in (89 mm) deep electrical boxes. Several devices 

can be installed in one electrical box (multigang). This requires derating of the dimming 

device. For a smooth appearance, one-piece multigang faceplates (not supplied) can 

be installed.

 

 

Mechanical 3- or 4-way switches do not work with CLW-DELVEX-E/P dimmers.

 

 

Spacing: If mounting one device above another, leave at least 4 1/2 in (115 mm) 

vertical space between them.

 

 

Low Voltage Applications: Use with electronic low voltage transformers only. Do not 

use any magnetic low voltage transformers. Operation of a low voltage circuit with all 

lamps inoperative or removed may result in current flow in excess of normal levels. To 

avoid transformer overheating and premature transformer failure, Crestron 

recommends the following:

    >  Do not operate low voltage circuits without operative lamps in place.
    >  Replace burned-out lamps as quickly as possible.
    >  Use transformers that incorporate thermal protection  to prevent transformer failure 

due to overcurrent.

INSTALLATION

WARNING

:  Turn off power at the circuit breaker. Installing with power on can result in 

serious personal injury and damage to the device.

CAUTION

:  New installations should be checked for short circuits prior to installing a 

CLW-DELVEX-E/P dimmer. With power off, close the circuit and restore power. If the 

lights do not work or a breaker trips, check and correct the wiring or fixture (if necessary). 

Install the dimmer only when the short is no longer present. The warranty is void if the 

dimmer is installed and operated with a shorted load.

The following describes the installation of a CLW-DELVEX-E/P dimmer.
  1.  Turn power off at the circuit breaker.
  2.  Wire the device as shown in the following diagram.

Connection  Wire Gauge 

Wire Color

HOT 

16 AWG 

Black

NEU 

16 AWG 

White

LOAD 

16 AWG 

Red

REM 

16 AWG 

Blue

GND 

16 AWG 

Green

White (NEU)

LOAD

Green

(GND)

Red (LOAD)

Black (HOT)

HOT

120V~

Blue (REM)

To One or More 

CLW-SLVU-P¹,² 

(Optional)

500 W

400 W

400 W

400 W

250 W

400 W

Changing Button Assemblies

The button assembly can be removed and replaced with other button assemblies. 
  1.  As shown in the following diagram, remove the button assembly by squeezing the 

sides of the bezel near the bezel snaps.

Squeeze at arrow 

points and pull to 

remove button 

assembly.

NOTE

:  When the button assembly is removed, power to the unit and load is 

removed automatically.

  2.  Remove button(s) from the front of the button assembly as shown in the following 

diagram.

  3.  Insert new buttons through the front of the bezel and snap into place as shown in the 

following diagram. Ensure that the LED strip is on the left side. 

  4.  Attach button assembly to the device as shown in the following diagram. Ensure that 

the LED strip is on the left side.

Gently spread frame 

apart to remove 

buttons.

Gently spread frame 

apart to insert 

buttons.

  5.  Once power has been restored, press and hold the right side of the air-gap switch 

(program button) as shown in the following diagram. After 5 seconds some LEDs start 

flashing. Continue to hold the button and proceed to step 6. 

  6.  While holding the program button, tap all of the buttons in the new layout. The LED 

next to the tapped button lights.

NOTE

:  If the rocker switch is installed, press the top and bottom of the rocker.

  7.  After all of the buttons have been tapped, release the program button to save the 

settings.

NOTE

:  Changing the button configuration alters the device’s behavior. Refer to  

"Default Button Functions" on the following page for details.

6

5

7

Press and hold 

the program 

button.

Release the 

program button 

to save the 

settings.

Tap each of the 

installed buttons 

on the device.

SPECIFICATION 

DETAILS 

Power Requirements 

120 Vac, 60 Hz 

Load Types 

Incandescent, tungsten-halogen, electronic low 

voltage transformers for low voltage halogen or LED, 

electronic CFL 

Load Ratings 
 

Minimum Load 

 

Maximum Load 

 
25 W 
500 W (Refer to the derating chart in the “Multigang 

Installations” section on this page.) 

Maximum Number of 

Remote CLW-SLVU-P 

Devices

1

 

Environmental 
 

Temperature 

 

Humidity 

 
32º F to 104ºF (0º C to 40º C) 
10 to 90% RH (non-condensing) 

Dimensions 
 

Height 

 

Width 

 

Depth 

 
4 1/8 in (105 mm) 
1 3/4 in (45 mm) 
1 13/16 in (47 mm) 

Weight 

5 oz (128 g) 

Operating Frequency 

2400 to 2483.6 MHz (802.15.4 compliant) 

Operating Ranges

 

Device to Gateway 

 

Device to Device 

 
150 ft (45 m) indoors; 250 ft (76 m) outdoors 
100 ft (30 m) indoors; 175 ft (53 m) outdoors 

Default RF ID 

01 

 

Further Inquiries

To locate specific information or resolve questions after reviewing this guide, contact Crestron's True Blue Support at 

1-888-CRESTRON [1-888-273-7876] or, for assistance within a particular geographic region, refer to the listing of 

Crestron worldwide offices at www.crestron.com/offices.

To post a question about Crestron products, log onto Crestron’s Online Help at www.crestron.com/onlinehelp. 

First-time users must establish a user account to fully benefit from all available features.

Future Updates

As Crestron improves functions, adds new features and extends the capabilities of the CLW-DELVEX-E and 

CLW-DELVEX-P, additional information may be made available as manual updates. These updates are solely 

electronic and serve as intermediary supplements prior to the release of a complete technical documentation 

revision.
Check the Crestron Web site periodically for manual update availability and its relevance. Updates are identified as 

an “Addendum” in the Download column.

WARNING: 

To avoid fire, shock, or death; turn off power at circuit breaker or fuse and test that power is off before 

wiring!

 

NOTES: 

Observe the following points.

•  To be installed and/or used in accordance with appropriate electrical codes and regulations.
•  This product should be installed by a qualified electrician.
•  Sensors must be mounted on a vibration free surface.

PREPARING AND CONNECTING WIRES

Strip the ends of the wires approximately 1/4 in (6 mm). Use care to avoid nicking the conductors. Twist together 

the ends of the wires that share a connection. Apply solder only to the ends of the twisted wires. Avoid tinning too 

far up the wires or the end becomes brittle.